Kitchen Exhaust Hoods A Performance Perspective
by Don Fisher, P.E.
September 1, 2009
 |
| FIGURE 1. Ten-foot wall-mounted canopy hood test setup with heavy-duty charbroilers(note transparent back wall). |
|
When
is listed cfm not an adequate criterion for selecting a kitchen hood
exhaust system? Well, just about always. Where is the hood located?
Does it use side panels? Any other diffusers or ventilation equipment
nearby? And how are those listing tests conducted, anyway? Read on to
clear the air and avoid getting grilled about trouble in one of your
kitchen applications. Hot
air rises, and an exhaust fan in the ceiling could easily remove the
heat produced by the cooking equipment. But mix in smoke, volatile
organic compounds, grease particles, vapor from cooking, and
combustion products, and you have a need for a means to capture and
contain the effluent to avoid health and fire hazards. While an
exhaust hood and its system components serve this purpose, the key
question is always, “What is the appropriate design exhaust rate?”
The answer always depends on four factors:
- The type, energy source, and use of the cooking equipment below
the hood
- The position of this cooking
equipment below the hood
- The style
and geometry of the hood itself
- How
the makeup air (conditioned or otherwise) is introduced into the
kitchen
 |
| FIGURE 2. Hood setup with and without side panels. |
|
But
does the design of the exhaust hood itself matter? Will the design
exhaust rate vary between hood manufacturers when all other
parameters remain (hopefully) constant? And what about the hood’s
listed cfm rating? “Hood capture and
containment” is defined by ASTM F1704-05, “Capture and
containment performance of commercial kitchen exhaust ventilation
systems,” as “the ability of the hood to capture and contain
grease laden cooking vapors, convective heat and other products of
cooking processes.” Hood capture refers to the products getting
into the hood reservoir, while containment refers to these products
staying in the hood reservoir and not spilling out into the space.
“Minimum capture and containment” is defined as “the conditions
of hood operation at which the exhaust flow rate is just sufficient
to capture and contain the products generated by the appliance in
idle and heavy load cooking conditions, or at any intermediate
prescribed load condition.” Pacific Gas &
Electric’s (PG&E) Food Service Technology Center (FSTC)
undertook an evaluation of wall-mounted canopy hoods from several
different manufacturers in accordance with the ASTM 1704 test method.
This testing was conducted at the Commercial Kitchen Ventilation
(CKV) Laboratory in Wood Dale, IL, with a generic unlisted hood
included in the test matrix. Each wall-mounted hood was 10 ft long
and was tested over standardized cooking equipment, including a
heavy-duty, medium-duty, light-duty, and mixed-duty product line. The
primary tools used for airflow visualization were schlieren and
shadow graph systems, which visualize the refraction of light due to
air density changes. Since the heat and
effluent generated by the cooking process change the air density
above the equipment, the system provides an image of the thermal
activity along the perimeter of the hood, confirming capture or
documenting spillage. By increasing or decreasing the airflow rate,
the threshold of capture and containment (C&C) was determined.
For this hood performance investigation, the replacement air was
supplied from low-velocity, floor-mounted displacement diffusers
along the opposite wall. Test results for the individual hoods can be
downloaded from the FSTC website at
http://www.fishnick.com/publications/appliancereports/hoods/. Figure
1 shows the test setup for a wall-mounted canopy hood over three
heavy-duty charbroilers. Note that the back wall is transparent to
permit the light from the schlieren system to pass through. Figure 2
illustrates the hood setup with and without the partial side panels.
The results of this heavy-duty appliance challenge are shown in
Figure 3 for four models of listed hoods and one unlisted hood.
Testing was conducted with the appliances
pushed as far back (towards the back wall) as possible to maximize
the overhang and minimize the rear gap, both positive attributes for
optimum hood performance. For one test in the “no-side panel”
configuration, the generic hood was pulled forward until the overhang
was only 6 in. In this case, the C&C rate increased dramatically.
For all hoods, the C&C rate decreased
when partial side panels were installed. The threshold of C&C
decreased even further when the gap between the back of the
appliances and the wall was flashed in with sheet metal. For
reference, the exhaust requirement for an unlisted hood from ASHRAE
Standard 154-2003, “Ventilation for Commercial cooking Operations,”
is shown as a solid line at the 400 cfm/ft mark. This also matches
the requirement in the International Mechanical Code (IMC) for an
unlisted hood. As illustrated, all of the
listed hoods were able to capture and contain the cooking effluent at
significantly lower airflow rates. Adding partial side panels and
sealing the gap between the appliance and wall resulted in an even
greater reduction in the airflow needed for total capture of the
effluent under full-load cooking. Note that the values shown are the
threshold of C&C under ideal conditions of makeup air supply and
no intrusion from staff walking along the cook line. A design value
needs to include a safety factor to accommodate for the dynamics of
the kitchen environment.
Listed Exhaust Hoods and The Fallacy Behind The ‘CFM’ Ratings
There
is often an underlying supposition that the exhaust hood will
function satisfactorily if it is specified in accordance with its
UL-listed airflow capacity. This may be far from reality.
For
example, a heavy-duty appliance such as a charbroiler at the end of a
mixed-duty appliance line is going to require a design exhaust
ventilation rate (based on the experience of the author and data
shown in Figure 3) of at least 300 cfm/ft for a wall-mounted canopy
hood (depending on the actual hood being specified). If side panels
are utilized, and overhang is maximized, this design number might be
dropped to 250 cfm/ft.
|
|
| FIGURE 3. Wall-mounted canopy test results with heavy-duty charbroilers. (CB/CB/CB stands for three charbroilers under full-load cooking.) |
|
However,
a quick survey of manufacturers’ listings on the UL website shows
minimum airflow rates in the range of 150 to 250 cfm/ft (without side
panels). And when one moves to a single-island hood application,
realistic design airflow for a heavy-duty challenge (600ºF)
such as the charbroiler need to be in the 600 cfm/ft range (based on
testing experience at the CKV Lab). But a query of the 600º
listings for single-islands hoods reveals values that are typically
under 300 cfm/ft. This huge gap between a listed cfm and what would
be a successful design cfm sheds light on the display-cooking
challenge. In the author’s opinion, single-island canopy hoods are
being specified with inadequate exhaust airflows for heavy-duty
appliance lines on most projects. Proceed with caution. To
fully grasp this predicament, one needs to understand how a listing
agency conducts their capture and containment (smoke and flare-up)
test in accordance with UL 710. For the case of a high-temperature
(600)
application (which would apply to a hood over a heavy-duty gas
charbroiler), the minimum and maximum length of a given hood model is
tested over an electric broiler (with cooking surface dimensions less
than 2 ft x 2 ft). This electric broiler (or maybe an electric
griddle with its thermostat cranked up), is installed at one end of
the test hood. The exhaust rate is increased until no visual smoke is
perceived to spill while the broiler is cooking a full load of 30%
fat hamburger patties. The exhaust rate under this capture condition
becomes the reported minimum cfm within the hood’s listing.
Now, anybody in the foodservice industry
understands that a 2 ft x 2 ft electric broiler does not produce the
equivalent heat and smoke of a commercial gas charbroiler, with
dimensions that would typically be 2 ft x 3 ft or 2 ft x 4 ft and
have rated inputs in the range of 100,000 to 140,000 Btuh. It becomes
obvious that a hood may not be able to capture the heat and smoke
produced by a gas broiler if the exhaust hood is sized according to
its minimum “cfm” listing for a 600
classification based on the smaller electric broiler. Taking
a more optimistic perspective, the exhaust rate required to ventilate
a mixed-duty appliance line (typical of an institutional kitchen with
a range top, broiler, fryer, steamer, and oven) may be closer to the
average of the ventilation requirement for the individual appliances.
Since codes dictate that the exhaust airflow be based on the heaviest
duty appliance under the hood, a hood installed over a mixed-duty
appliance line may work OK if it is sized based on the hood’s
listed cfm for a 600 application. But
if the broiler is placed at the end of the cookline and side panels
are not utilized, the capture and containment performance will be
compromised. Add in a four-way diffuser near the hood, and the
situation goes from bad to worse and the phone starts to ring.
Take-Home Tactic
There
is a silver lining within this cloud of concern about the listed
cfm. The fact that listed hoods have been rated at
airflows that are well below the prescriptive requirements for
unlisted hoods allows the designer to select an effective exhaust
flow rate that is in between the two cfm numbers. Rather than
gambling on the listed exhaust rate, the designer should utilize hood
manufacturers’ software or calculations to select an appropriate
design value for a given project. And one last bit of advice. Hold
“spec” on the design exhaust cfm; it should not be negotiable
within the competitive bid and the consideration of alternative
ventilation system proposals that are put forward based on lower
listed cfm values. Consider specifying exhaust airflow performance
based on the ASTM 1704 test protocol.
Once you
have spec’d out what you think is the best hood for the project,
remember the ability of that exhaust hood to C&C the effluent
produced by the cooking equipment is a function of much more than the
physical attributes of the hood.
Unfortunately,
many of these influencing factors are overlooked in the detailed
specifications (e.g., appliance positioning beneath the hood or the
delivery path of the replacement air). Beneficial design factors,
such as overhang, hood height, side panels, or end walls may be
downplayed in terms of their significance and neglected within the
specifications. Specifying a top-of-the-line exhaust hood is
important, but it is only the first step in designing a
high-performance kitchen ventilation
system.
Acknowledgments
The
author would like to recognize the hood research conducted at the CKV
Laboratory in Wood Dale, IL, by Rich Swierczyna, Paul Sobiski, and
Rick Gliva, with Architectural Energy Corporation. All hood
performance data shown in this article was provided by the CKV Lab
with financial support from PG&E. ES
|