This website requires certain cookies to work and uses other cookies to help you have the best experience. By visiting this website, certain cookies have already been set, which you may delete and block. By closing this message or continuing to use our site, you agree to the use of cookies. Visit our updated privacy and cookie policy to learn more.
This Website Uses Cookies
By closing this message or continuing to use our site, you agree to our cookie policy. Learn More
This website requires certain cookies to work and uses other cookies to help you have the best experience. By visiting this website, certain cookies have already been set, which you may delete and block. By closing this message or continuing to use our site, you agree to the use of cookies. Visit our updated privacy and cookie policy to learn more.
ES Magazine logo
search
cart
facebook twitter linkedin youtube
  • Sign In
  • Create Account
  • Sign Out
  • My Account
ES Magazine logo
  • Home
  • Magazine
    • Current Issue
    • Digital Edition
    • Ad Index
  • Products
  • News
  • Sectors
    • Colleges/ Universities
    • Commercial
    • Government/ Institutional
    • Health Care
    • Hospitality
    • K-12
    • Mission Critical
  • Topics
    • Building Automation
    • Cooling & Chillers
    • Design/ Construction Process
    • Heating & Boilers
    • IAQ
    • Life Safety
    • Motors & Drives
    • Pumps & Flow Controls
    • Retrofits
    • Ventilation
  • Columns
    • Back2Basics
    • Building Automation Column
    • Case In Point
    • Commissioning
    • Editor's Note
    • Facility Files
    • IAQ: A Physician's View
    • Tomorrow's Environment
  • Multimedia
    • Videos
    • Podcasts
    • Webinars
    • Video Spotlights
    • Interactive Spotlights
    • Sneak Peek Spotlight
    • White Paper eBlast
    • Case Study eBlasts
  • Resources
    • eNewsletters
    • Continuing Education
    • White Papers
    • Industry Events
    • ES Store
    • Classifieds
    • Custom Content & Marketing Services
    • Market Research
  • Today's Boiler
    • Today’s Boiler Digital Edition
  • Directory
    • SourceBook
    • Take a Tour
  • Contact
    • Contact Us
    • Advertise
Home » Safety Valve Requirements For Deaerator Installations: How Much Relief?
Heating & BoilersToday's Boiler

Safety Valve Requirements For Deaerator Installations: How Much Relief?

Crane_Img01_Slide.jpg
Safety relief valve shown mounted on the steam line after the steam pressure reducing valve.
Crane_Img02_Slide.jpg

Minimum sentinel relief valve size per HEI standards shown mounted on deaerator vessel. A full-size safety relief valve is also provided elsewhere on the system.

Crane_Img01_Slide.jpg
Crane_Img02_Slide.jpg
June 8, 2012
Crane Environmental
KEYWORDS exhaust / valves
Reprints
10 Comments

Learn about the proper location for those valves, managing blowoff steam and turbine exhaust, and more.

Very few deaerators utilize vessels that are not constructed and stamped in accordance with ASME VIII Pressure Vessel rules.

The ASME Code requires that all pressure vessels be protected against overpressure from any source, if not by positive control of the pressure source then by the use of properly sized relieving devices.

What are the sources that could result in loss of deaerator pressure control? The most likely sources are discussed below. In all cases, the worst-case scenario would occur if the deaerator load is zero due to high water level and/or temporary diversion of low-temperature condensate returns away from the deaerator.

STEAM PRESSURE REDUCING VALVES

A deaerator requires a source of heat in the form of steam to heat the feedwater to saturation and to remove dissolved gases. For many deaerators, this source of steam is high-pressure steam reduced to the desired deaerator operating pressure by a steam pressure control valve.

In the event of a steam pressure control valve failure, an excess flow of steam will be provided to the deaerator, causing the deaerator pressure to rise. In the worst conceivable case, the maximum excess steam flow may be considered to be the steam flow which the pressure reducing valve can pass with the usual supply pressure on its upstream side and deaerator design pressure on its downstream side. This assumes that the valve has failed in the wide open position and that the deaerator load is zero (i.e., the deaerator has a zero steam demand).

The wide open capacity of pressure control valves can be obtained with the valve manufacturer's assistance or can be calculated from data in the form of maximum flow coefficients for the valve(s) installed in the system.

HIGH-PRESSURE CONDENSATE RETURNS

High-pressure (HP) condensate is condensate that is produced at a temperature greater than the operating temperature of the deaerator. The usual sources of this condensate are process equipment (cookers, driers, etc.) and heat exchangers.

In some plants, this HP condensate is drained to a receiver where its pressure and temperature is reduced to atmospheric conditions (0 gauge pressure, 212°F or less). Pumps are then used to transfer the 'flashed" condensate to the deaerator. Under these conditions, the HP condensate does not present a risk of overpressurizing the deaerator. However, in many situations where it is desired to conserve heat, HP process condensates may be returned directly to the deaerator. In these cases, the excess heat in the condensate must be absorbed by colder streams (e.g., makeup water and cool condensates) entering the deaerator if the deaerator pressure is to be controlled at a steady level. Heat not absorbed goes into elevating the operating temperature and pressure within the deaerator. If the condensate can produce a positive amount of flash steam when reduced to the deaerator design pressure, that amount of flash steam should be included in the safety valve capacity requirement.

CONTINUOUS BLOWOFF / RECOVERED STEAM

In plants using a continuous blowoff heat recovery system, the flash steam produced by the blowdown is usually directed to the deaerator so that its heat content can be recovered. As with HP condensate returns, if the deaerator is operated at loads capable of utilizing the heat in this steam, the deaerator pressure can be controlled at a desired level. If the deaerator load is such that there is insufficient demand for the blowoff steam, the pressure in the deaerator will rise above the control point unless the excess steam is relieved.

Safety valve capacity required to protect against overpressure due to excessive continuous blowoff may be determined by calculating the amount of flash steam produced when the maximum blowoff flow is flashed to a pressure equal to the design pressure of the deaerator and that amount of flash steam should be included in the safety valve capacity requirement. The maximum blowoff flow to be considered is a function of boiler pressure, the number, size, and setting of the blowoff valves as well as the blowoff line size.

TURBINE EXHAUST

In some installations, the steam supply to the deaerator may consist of steam turbine exhaust, augmented with reduced high-pressure steam (described above). If the maximum turbine exhaust pressure exceeds the deaerator design pressure, safety valves must be provided to protect the deaerator; otherwise, relief or safety valves will be needed to protect the turbine. Since the worst case for excessive turbine exhaust flow would occur at zero deaerator load, the safety valve capacity needed to protect against overpressure due to a turbine exhaust is equal to the throttle flow of all turbine(s) connected to the deaerator steam line. Maximum throttle flow information can be obtained from the turbine manufacturer.

LIQUID STREAMS

If the pressure of any feedstream to the deaerator exceeds, or may exceed, deaerator design pressure, adequate relieving capacity must be provided to protect the unit against overpressure from that source. Consideration should be given to the shutoff heads of feedpumps and water supply pressures as well as to the steam sources described above. Usually, the safety valves required for liquid relief alone would be considerably smaller in size than those required for steam relief.

SAFETY VALVES PROVIDED BY THE MANUFACTURER

Usually, the deaerator manufacturer will not provide full capacity safety valves with his equipment. When specified to be within this scope of supply, the deaerator manufacturer can size and supply the required safety valves only when the user or plant designer has supplied all needed details related to sources of overpressure in his system. In the absence of complete information, the deaerator supplier may furnish relief valves in accordance with the HEI Standards For Deaerators. The safety valve number and sizes recommended by the HEI standards are determined on an arbitrary basis and are intended to protect the deaerator against overpressure due to minor sources of overpressure, such as the introduction of excess amounts of HP condensate. However, the HEI-recommended safety valve sizes should be considered as minimums and to ensure a compliant installation, their adequacy for any application should be verified.

SAFETY VALVE REQUIREMENTS

The ASME Code requires that sufficient relief valve capacity be provided to prevent the pressure inside the deaerator and storage tank from rising more than 10% or 3 psi, whichever is greater, above the maximum allowable working pressure of the vessels when a single safety valve or relieving device is utilized. When multiple safety valves are utilized, the set pressures of the individual devices may be staggered as permitted in paragraph UG-134 of the code. Safety valves on deaerators are normally set to relieve at maximum allowable working pressure of the vessels.

Safety valves for use on ASME Code vessels must meet the manufacturing and certification requirements set by the Code and outlined in Paragraphs UG-125 through UG-136 of ASME Section VIII, Division 1.

LOCATION OF SAFETY VALVES

The ASME Code requires that safety valves intended for relieving steam be connected to the steam space of the pressure vessel when the source of overpressure is internal to the vessel. For this reason, it is common to connect the safety valves to protect against overpressure due to excessive flashing returns directly on the deaerator. If the source of overpressure is external to the pressure vessel, the ASME Code does not require the safety valves to be installed directly on the vessel. It is for this reason that the full capacity safety valves, whether provided by the purchaser or the deaerator manufacturer, are not normally located on the deaerator but on the piping connecting the deaerator to the source. In this way, the deaerator is protected and the risk of internal damage due to steam flows in excess of design is minimized.

OPERATION

The reaction-type safety valves normally used are characterized by 'pop' action where the valve is rapidly pushed to the wide open position shortly after set pressure is exceeded. The safety valve remains open until such a time that vessel pressure has been reduced to a value approximately 5% below the set pressure of the safety valve. This difference between set pressure and reseating (closing) pressure is termed blowdown.

Due to these operating characteristics, it is important to consider the potential effects of safety valve operation on the deaerator. Consider a deaerator operating at a controlled pressure of 10 psig but designed for 50 psi maximum allowable working pressure with a safety valve set at 50 psi. If for some reason, the deaerator is supplied with more heat input than can be absorbed at 10 psig by the incoming water, the deaerator pressure will begin to rise. The deaerator will heat the incoming water to the saturation temperature corresponding to each new (higher) operating pressure and this water will be held in the storage vessel. If the excess steam condition persists, the pressure in the deaerator will continue to rise toward the safety valve setpoint. Just prior to actuation of the safety valve, 50 psi in this example, the deaerator will be delivering water at 298° to the storage tank.

At the set pressure, the safety valve opens and soon reaches full open position; the deaerator is delivering water heated to 298° to 302° to the storage vessel all while the safety valve is blowing. As the source of overpressure begins to diminish, the safety valve remains open until the pressure in the deaerator decreases to approximately 45 psig. During the time period when the deaerator pressure is decreasing toward the control point (10 psi), the hot stored water is cooling to saturation temperature by flashing and steam is flowing from the storage tank to the deaerator through the equalizers. If possible, water flow rates should be controlled for slow rates of change during a safety valve blowing operation; at rapid rates of change, the deaerator may be subject to damage as a result of rapid depressurization.

Installation of relief valves in parallel with the safety valves on deaerator installations can prevent unnecessary activation and ‘chattering’ of the safeties from minor upsets in pressure control, e.g., situations where a discharge of steam considerably less than the combined safety valve capacity would suffice to prevent overpressurization. In contrast to safety valves (pop action to full capacity), relief valves open only in proportion to the amount of overpressure present, preventing excessively high discharges from slight disturbances. Many older boiler plants were equipped with relief valves in this manner but the practice has waned in the recent past. However, the prevention of frequent safety valve discharges remains a worthwhile goal to reduce noise emissions and maintenance requirements.

CONCLUSION

The information provided above is intended to illustrate typical procedures for determining the maximum flows to a deaerator which might overpressure the unit and provide a basis for sizing of relief valves. Since the design of each installation varies, the user is responsible for identification of all potential sources of overpressure and provision of sufficient relief valve capacity to ensure safe operation of the deaerator.  TB

es-subscribe

Related Articles

Safety relief valves

Safety-relief valves

CRANE ENVIRONMENTAL- Deaeration: Why & How in Industrial Water Cooling

Valves Spells ‘Relief' For New Jersey School District

Related Products

Lessons Learned in a Boiler Room: A common sense approach to servicing and installing commercial boilers

BIM Handbook: A Guide to Building Information Modeling for Owners, Managers, Designers, Engineers and Contractors - 3rd Edition

Electricity, Electronics, and Control Systems for HVAC, 4/e

Engineered Systems April 2019 Issue

Related Directories

McGill AirPressure LLC

Metal Industries Inc.

Safety Technology International (STI)

You must login or register in order to post a comment.

Report Abusive Comment

Subscribe For Free!
  • Print & Digital Edition Subscriptions
  • eNewsletters
  • Online Registration
  • Subscription Customer Service

More Videos

Popular Stories

Dynamic Data Center Workloads Require a Dynamic Cooling Solution

Dynamic Data Center Workloads Require a Dynamic Cooling Solution

Protecting Pharmacists

Protecting Pharmacists: New USP 800 Standards Focus on Safety in Handling Hazardous Drugs

The Dangers of Neglecting Regular Boiler Maintenance

The Dangers of Neglecting Regular Boiler Maintenance

A2L Nov 2019 Figure 1

A2L Refrigerants: Safely Addressing Flammability Concerns

Jeff Edwards

Jeffrey W. Edwards Presented with ASPE Award of Merit

ES-20toWatch-winners250


Todays boiler

Events

December 30, 2030

Webinar Sponsorship Information

For webinar sponsorship information, visit www.bnpevents.com/webinars or email webinars@bnpmedia.com.

View All Submit An Event

Poll

Favorite Engineered Systems columns

Which Engineered Systems column is your favorite:
View Results Poll Archive

Products

The Green Energy Management Book

The Green Energy Management Book

Learn from our experts how to evaluate job opportunities, market your services, sell a Walk-through Survey, target areas for an Energy Audit, calculate energy savings, do retrofit work, and win continuing contracts for retrofit work.

See More Products

ES Kohler webinar


ES_2018Top10States_360

Engineered Systems Magazine

Engineered Systems December 2019

2019 December

Check out the December 2019 edition of Engineered Systems: Discussion of the "next generation" of building controls, the health impact of indoor particulate matter, evidence-based decision-making in the built environment and much more!
View More Create Account
  • Resources
    • ES Glossary
    • HVAC glossary
    • New Products
    • Mechanical Group
    • Partners
    • List Rental
    • Privacy Policy
    • Survey And Sample
  • Want More
    • Connect
  • Contact

Copyright ©2019. All Rights Reserved BNP Media.

Design, CMS, Hosting & Web Development :: ePublishing