WHY DEAERATE?
HOW?

Figure
2. The effect of partial gas pressure and heating.
Mechanical
agitation. The heated water must be mechanically agitated by spraying,
cascading over trays, or by atomization to expose maximum surface contact to
the scrubbing atmosphere, thus permitting complete release and removal of
gases. When water is broken down into fine droplets for thin films, the
distance that the gas bubble must travel for release is greatly decreased.
Thorough agitation also overcomes tendencies of surface tension and viscosity
to retain the gas bubbles and increases the rate of gas diffusion from the liquid
to the surrounding atmosphere. The deaerating equipment, therefore, must
provide the most efficient mechanical agitation possible to permit meeting
modern requirements of gas removal. Since a normal warranty of “not to exceed
0.005 cc per liter of oxygen” means less than 7 lbs in a billion pounds of
water, the importance of effective agitation cannot be overstressed.
Complete gas removal. Adequate steam must be passed through the water to scrub
out and carry away the gases after release. Extremely low partial gas pressure
must be maintained since Henry’s Law states that the amount of gas which will
dissolve in a liquid is proportional to the partial gas pressure in the
atmosphere contacting the liquid. It is mandatory that the volume of scrubbing
steam be high to produce the low partial gas pressure, and it is equally
mandatory that these conditions prevail throughout the deaerating section. The
effect of partial gas pressure and heating is illustrated in Figure 2.
DEAERATOR TYPES
There
are five principle types of deaerators: parallel flow tray, counterflow tray,
scrubber spray, atomizing spray, and cold water. All designs employ the
cardinal principles of deaeration outlined above and are capable of delivering
water with a dissolved oxygen removal to ensure the effluent contains 7 ppb or
less.
Tray deaerators. Tray (or spray-tray) units are most widely used for deaerating
boiler feedwater in industrial plants and central generating stations. Water is
heated to full saturation temperature with minimum pressure drop and minimum
vent, thereby ensuring best thermal efficiency. Deaeration is accomplished by
spreading the water over multiple layers of trays designed to break the water
into thin films and drops to promote intimate contact with the scrubbing steam.
Parallel downflow designs provide maximum flexibility for application, and it
will handle any combination of condensate and makeup. Counterflow designs
provide best economy for plants having low makeup requirements (higher
condensate return percentage).
Spray-deaerators. These are widely used in industrial plants where treated
water makeup is dominant over condensate returns. The most common spray
deaerator features a scrubbing device where steam and water are mixed to
provide the contact and agitation necessary for a high level of dissolved
oxygen reduction. “Scrubber” deaerators are simple and economical with low
maintenance but do not perform well at reduced loads. The “atomizing” variation
of the spray deaerator was developed for use in marine vessels to accommodate
low load operation and are an option to the scrubber-type designs when high
load-turndown capability is needed. Atomizing deaerators use an internal valve
that varies the steam injection opening to suit the load where the fixed
openings used in scrubber type units do not have this ability. Because the
atomizing device has moving parts, it adds to the cost and requires more
maintenance effort than the scrubber type design.
Cold water deaerators. Cold water deaerators are used primarily to eliminate
corrosive gases from cooling water or water used in food processing, where it
would be undesirable to increase the water temperature or risk contamination
due to contact with the volatile chemicals present in the usual steam supply.
To replace the addition of steam that is characteristic of the usual tray and
spray deaerators, a boiling condition is created in a cold water deaerator by
pressure reduction using vacuum-producing equipment. Surface contact with
scrubbing vapor and agitation is provided by a column of mass transfer packing
in lieu of trays, scrubbers, or atomizing devices.
CONCLUSION
The
benefits of deaeration of boiler feed and process water has become so well
recognized that even small plants now ensure longer equipment life and reduced
maintenance by employing some type of deaeration.
Deaeration today is an important factor in the successful and economical
operation of any modern boiler plant, regardless of its size.
TB