FIGURE 1. An exploded view of layered air treatment technologies adapted to the mixing box section of an AHU. (Courtesy of Genesis Air, Inc.)


Photocatalytic oxidation (PCO) is an emerging technology in the HVAC industry that has great potential for application toward improvement of IAQ. In addition to the prospect of IAQ benefits, it has the added potential for limiting the introduction of unconditioned air to the building space, thereby presenting an opportunity to achieve energy savings over classical prescriptive designs. As with other advanced oxidizing technologies, sound engineering principles and practices should be employed by the building HVAC designer to ensure proper application of the technology. The purpose of this document is two-fold: (1) to present a general overview of guidance materials, standards, and other considerations that should be taken into account during evaluation of PCO for use in building HVAC designs; and (2) to introduce a specific methodology for approaching the task of providing engineered designs that successfully incorporate PCO and complementary technologies.

TERMINOLOGY

A short glossary of terms is included to familiarize the reader with the similarities, differences, and relationships between various technologies addressed in this document.

Heterogeneous Photocatalysis1. Photocatalysis taking place at the interfacial boundary between two phases (solid-liquid, solid-gas, liquid-gas).
UV Germicidal Irradiation1. (UVGI or UVC): Photolysis in which microbes are killed or neutralized by exposure to ultraviolet light at wavelengths at or near 2,537 Angstroms, or 253.7 nanometers. Irradiation at this wavelength damages their molecular structure by altering DNA and RNA.
Ventilation Rate Procedure2. ASHRAE 62.1 defines this as a prescriptive procedure in which outdoor air intake rates are determined based on space type/application, occupancy level, and floor area. Note: The Ventilation Rate Procedure minimum rates are based on contaminant sources and source strengths that are typical for the listed space types.
IAQ Procedure2. ASHRAE 62.1 defines this as a design procedure in which outdoor air intake rates and other system design parameters are based on an analysis of contaminant sources, contaminant concentration targets, and perceived acceptability targets. This procedure allows credit to be taken for controls that remove contaminants (e.g., air cleaning devices) or for other design techniques (e.g., selection of materials with lower source strengths) that can be reliably demonstrated to result in indoor contaminant concentrations equal to or lower than those achieved using the Ventilation Rate Procedure. The IAQ Procedure may also be used where the design is intended to attain specific target contaminant concentrations or levels of acceptability of perceived IAQ.
LEED® Certification3. LEED is a consensus-based national standard for developing high-performance, sustainable buildings. Certification distinguishes building projects that have demonstrated a commitment to sustainability by meeting the highest performance standards.
Particulate Filtration4. The capture of small airborne particles found in indoor and outdoor environments. These particles include fibrous materials, solid-state semi-volatile organic compounds, and biological materials.
Photocatalysis5: The acceleration of a photoreaction in the presence of a catalyst. The photocatalytic activity depends on the ability of the catalyst to create electron-hole pairs, which generate free radicals able to undergo secondary reactions such as oxidation.
Photolysis5: A chemical reaction in which a compound is broken down by light. The direct process is defined as the interaction of one photon with one target molecule.


TECHNOLOGY INTERACTION

"The perception of indoor air quality is based on the interaction of a complex set of variables including chemical, biological, physical, and psychosocial factors. Concern about indoor air quality has been driven mainly by health problems believed to be attributed to exposure to gaseous, particulate and microbial contaminants."6

Methods of addressing these types of contaminants in building airstreams have yielded successful results for improvement of IAQ. As most occupied building spaces contain indoor air that harbors all three of these contaminant types, a multi-layered approach to the use of common and emerging technologies is often required to address the variety of contaminants. Some of these technologies share complementary relationships with others and lend themselves well to combined use.

An example of the complementary relationship between technologies can be found in the combined use of particulate filtration, photolysis, and photocatalysis. With proper equipment placement and maintenance, particulate filtration can capture and remove from free circulation many dusts, pollens, and other particulate matters in an airstream, while allowing smaller particulates, microbes, and gases to pass through the filters.

UVGI exposure can then neutralize many of the microbial contaminants that were not picked up by the particulate filters. With careful positioning and adequate density, photons emitted by the UV lamps can also activate the PCO process, allowing the creation of hydroxyl radicals that aggressively oxidize gaseous, particulate, and microbial contaminants that pass through the media.

Careful coordination of these technologies is paramount to their successful application in the improvement of IAQ. The efficiency of the particulate filter, described by its MERV rating, is affected by the velocity of the air moving across the filter. Refer to ANSI/ASHRAE Standard 52.2 for detailed information concerning MERV ratings and related performance parameters.

Similarly, UVGI effectiveness is related to airborne contaminant velocity, since it is directly based on the intensity of photon exposure to the contaminant and to the amount of exposure time. As might be expected, PCO efficiency is affected by the velocity of air moving through the media, since it determines residence time, which is the amount of time the hydroxyl radicals have to complete the redox process. PCO efficiency is also dependent upon configuration to allow sufficient photon energy (3.2eV for TiO2) to reach the full surface of the semiconductor such that hydroxyl production can be maximized.

APPLICATION DESIGN OBJECTIVES

Indoor air treatment by layered PCO equipment is categorized in ANSI/ASHRAE Standard 62.1 as an IAQ Procedure, which allows the design professional the opportunity to choose an alternative to the prescriptive method: the Ventilation Rate Procedure. The resulting benefits are designs that can minimize the over-use of outside air to dilute odors and other contaminants, a procedure often associated with high energy usage8,9and, in some instances, a source of introduction of additional airborne contaminants to the building space. The designer should conduct airstream sampling and constituent characterization to gain a clear understanding of which airborne contaminants are present prior to determining how to apply air treatment technologies to specific building spaces. If there are no opportunities for sampling and characterization, historical data relating to the quality of indoor air at nearby facilities of similar function and operating schedule should be examined.

Data regarding outdoor air quality should also be gathered to account for the introduction of outside air to the building spaces of concern. Occupancy load data is necessary for the designer to gain a proper understanding of how airborne contaminants might be distributed within the building spaces. Process chemicals that are stored or applied within the building confines or adjacent exterior areas in communication with the target spaces must be documented and taken into account during design.

IAQ goals should be established for spaces under consideration for air treatment, as well as a means for determining adherence to those goals. In areas such as cleanrooms, surgical suites, and other highly regulated spaces, IAQ criteria are clearly defined. In spaces such as hotels, offices, classrooms, auto shops, and others, these criteria may not be as well-defined. General use IAQ goals can be adopted, but do not provide the level of guidance toward proper application of treatment technologies that can be provided by specific use goals.

In addition to site-specific abatement needs, a number of governmental, industrial, scientific, and private concerns are currently undertaking standards development efforts to set prescriptive categorical threshold limit values for exposure to specific contaminants of concern. Design professionals have the growing responsibility of keeping abreast of these regulatory developments and implementing them in their facility designs as they are adopted.

EQUIPMENT CONFIGURATION

Once contaminant species and concentrations are documented and IAQ goals are established, the designer's attention can turn to the task of matching layered air treatment technologies to the building spaces in which they are to be applied. Contaminant distribution profiles should be developed for each target building space. Control volume models can be constructed to account for the introduction and removal of air from zones. Contaminants introduced into the zonal airstreams by occupants and other generators can then be added to complete the air distribution models.

Deployment of building air treatment technologies is accomplished by two methods, the first being system-wide or general use, and the second being task-oriented or point-of-use. Often a combination of both methods is necessary for adequate treatment of the building air. Gaseous contaminants such as general odors and volatile organic compounds (VOCs) can spread rapidly throughout a building and at times are not readily associated with a particular process or area, and so they are treated by incorporation of layered PCO equipment into the building HVAC systems. It is desirable, however, to treat contaminants that are segregated to identifiable spaces and comprised in part or wholly of visually detectable particulates or gases, with point-of-use layered PCO equipment to prevent further dispersion of the contaminants throughout spaces that would otherwise not have co-mingled airstreams.

Some geographic locales require building designs that treat outside air before it enters the building air distribution system, due to high contaminant levels at the building exterior. Layered PCO can be used very effectively in this type of application. While this discussion has focused primarily on fixed-location PCO equipment use, opportunities are also common for its use in applications that require portable equipment for abatement of contaminants, such as office space refurbishing operations, concert venues, conventions, and other short-term space-using functions.

In placing air treatment equipment on a project, the designer should always be cognizant of local building codes, ordinances, and other applicable regulations, so as not to cause conflicts with life safety systems, fire and smoke barriers, space pressurization profiles, specialized air distribution systems, or other similar concerns.

ADDITIONAL CONSIDERATIONS

Advanced oxidizing technologies such as PCO systems readily support functional enhancements commonly associated with BAS. Standard practices of monitoring and reporting the loading of particulate filters, amperage draw of UV lamps, and operational status of fans are always recommended. Additional monitoring of occupant load by indicators such as CO2 or other methods, and of specific contaminants of concern, such as smoke obscurity and VOCs, can increase the data available to the BAS for increased system control. These monitoring points and control algorithms are supported by most energy monitoring and control platforms, such as BACnet®- or LonWorks®- compliant systems.10,11

Photocatalysis is considered to be a sustainable technology in that it functions to improve IAQ and minimize building energy usage, and does so without appreciable depletion of the semiconductor photocatalyst. In certain designs, the opportunity may exist for the LEED point standing to be increased due to the application of this technology to the building design.

As mentioned earlier, PCO can be applied in conjunction with other technologies to achieve specific design goals. In cases where granular activated carbon (GAC) systems are used to abate high concentrations of VOCs, PCO may be a good fit for placement upstream of the GAC unit to reduce contaminant concentration prior to entering the GAC filters, thus prolonging the useful life of the GAC media and reducing the cost of recharge or replacement.

In similar fashion, layered PCO technologies could be positioned adjacent to energy wheels or AHU coils so that the UVGI lights could bathe the equipment to preclude the promotion of unwanted microbial activity.

IN SUMMARY

A layered approach to the design and application of photocatalytic, photolytic, and other advanced air treatment technologies allows for complementary technologies to work together to improve the overall efficiency of the contaminant abatement effort.

A clear understanding of contaminant types, sources, and levels should be gained in order to effectively design and apply the treatment equipment in buildings or other enclosed spaces. Consideration should be given to ventilation requirements for occupant load, space pressurization, and building equipment needs. Facility air distribution patterns should be studied and fully understood such that placement of air treatment equipment will not disrupt the proper function of other building systems. Methods should be established to monitor performance of IAQ-improving technologies, and preventative maintenance schedules should be employed for the equipment. Placement of PCO units should be made to address system-wide and/or point-of-use solutions to specific contaminant problems.

With proper consideration to these design criteria, advanced oxidizing technologies can have dramatic impacts on the improvement of indoor environments.ES