Basics For Absorption Chillers
by Vincent A. Sakraida, P.E.
March 1, 2009
|
|
| FIGURE 1. Single-effect absorption refrigeration cycle. |
|
If
motor-driven vapor compression chillers are much more energy
efficient than absorption chillers, then why are we even having this
conversation? In a hunt for LEED® points or in applications with
certain demands, absorption could be just the ticket to
sustainability and/or economy.
Does
the idea of using steam, hot water, or direct-fired burners to
generate chilled water sound like an oxymoron? Well, absorption
chillers use these thermal energy sources to produce chilled water.
Beyond the type of thermal energy source, absorption chillers are
also classified by whether they are single- or double-effect. The
goal of this article is to provide the reader with a basic
description of absorption chillers and their advantages, specific
applications, performance standards, and energy efficiency, plus how
they can be used to gain LEED® certification points.
Water As A Refrigerant
How
about using water as a refrigerant and lithium bromide as a salt to
absorb the water? These are certainly not easily understood concepts.
However, water has a very high specific heat and latent heat of
vaporization, which makes it a great refrigerant. How
is water boiling at 212°F going to create chilled water at 44°?
First, the boiling temperature of water is a direct function of
pressure and at a pressure of 1 atmosphere (29.92 Hg), water boils at
212°. When the pressure on the water is decreased, the water boiling
temperature is lowered. The following table gives the total pressure
in inches of mercury and the corresponding approximate water boiling
temperature at different pressures:
| Absolute
pressure |
Water boiling point (°F) |
| 29.92
Hg (1 atm) |
212° |
| 2.99 Hg (0.1
atm) |
115° |
| 1.01 Hg |
80° |
| 0.30 Hg (0.01 atm) |
45° |
| 0.23
Hg |
38° |
Absorption chillers have
substantially reduced internal pressures to take advantage of the
lower water boiling temperatures. Absorption chiller internal
pressures can range from 0.1 atmosphere (atm) to below 0.01 atm.
Absorption Chiller Description
There
are a number of absorption chillers available, including
single-effect indirect-fired (steam, hot water); double-effect
indirect-fired; and double-effect direct-fired (gas and/or oil
burner). Single-effect absorption chillers have a single
generator/concentrator and condense all vaporized refrigerant in a
single condenser. Double-effect absorption chillers have two
generator/concentrators and the vaporized refrigerant from the high
temperature generator/concentrator is the thermal source for the low
temperature generator/concentrator, reducing the cooling requirement
for the vaporized refrigerant.
Single-effect
indirect-fired chillers are typically available in capacities between
100 and 1,350 tons with one manufacturer providing a unit up to 2,000
tons. Double-effect indirect-fired chillers are typically available
in capacities between 100 and 1,500 tons, although one manufacturer
provides a unit up to 5,000 tons. Double-effect direct-fired chillers
are typically provided in capacities between 100 and 1,500 tons.
|
|
| FIGURE 2. Double-effect absorption refrigeration cycle. |
|
A
description of the various single-effect, indirect-fired absorption
chiller components is provided below followed by a description of the
double-effect absorption chiller component that is different than the
single-effect absorption chiller. Single-effect
absorption chiller. The single-effect indirect-fired
absorption chiller has five main steps (Figure 1): condensing
(condenser), expansion (expansion pipe), evaporation (evaporator),
absorption (absorber), and generator/concentrator. See Figure A for
schematic chiller diagram and Diagram 1 for the Duhring
pressure/temperature diagram. Like the vapor compression chillers,
absorption chillers have a high-pressure side
(generator/concentrator, condenser) and low-pressure side (expansion
pipe, evaporator, absorber). The following component descriptions
will include some available options and standard operating
parameters:
- Condenser. In the condenser, the cooling water absorbs
the heat of condensation from the vaporized refrigerant, changing the
refrigerant into a liquid.
- Expansion. The liquid refrigerant (water) travels from
the condenser (0.1 atm) through expansion piping to the evaporator
(less than 0.01 atm) during which the liquid refrigerant experiences
a drop in pressure and temperature. The liquid refrigerant is
discharged into a pan within the evaporator.
- Evaporator. The liquid refrigerant (water) is pumped
to the chilled water tube bundle top and sprayed on the tube bundle.
At the low evaporator pressure (less than 0.01 atm), the liquid
refrigerant vaporizes at approximately 38°, removing energy from the
chilled water. Most lithium bromide absorption chillers can only
produce chilled-water supply temperatures down to 40°. Liquid
refrigerant that is not vaporized drops down to the pan and is
recirculated. Liquid refrigerant that is vaporized travels from the
evaporator to the absorber.
- Absorber. The vaporized refrigerant enters a liquid
lithium-bromide solution spray within the absorber. The lithium
bromide solution absorbs the vaporized refrigerant and the cooling
water absorbs the heat of vapor absorption. After the absorption, the
liquid lithium-bromide solution takes one of two paths. One path has
the liquid bromide solution mixing with a concentrated lithium
bromide solution and being pumped to the absorber spray nozzles. The
other path has the liquid bromide solution being heated and pumped to
the generator/concentrator.
- Generator/concentrator. The lithium-bromide solution
enters the generator/concentrator and is heated by steam or hot
water, raising the lithium bromide solution to a temperature where
the liquid refrigerant (water) vaporizes and travels to the
condenser, completing the refrigerant cycle. The concentrated lithium
bromide solution flows down to the absorber, completing the absorber
cycle.
- Double-effect absorption chiller. The double-effect
chiller condensing (condenser), expansion (expansion pipe),
evaporation (evaporator), and absorption (absorber) steps are the
same as the single-effect chiller. The double-effect chiller has an
additional generator/concentrator step that improves the overall
efficiency of the chiller (Figure 2). The following is a description
of the double-effect chiller
generator/concentration.
- Generator/concentrator. The lithium-bromide solution
enters the low-temperature generator/concentrator and is heated by
the high temperature generator/concentrator vaporized refrigerant,
raising the lithium-bromide solution to a temperature where the
liquid refrigerant vaporizes and travels to the condenser. The
high-temperature vaporized refrigerant discharges into the condenser.
The
concentrated lithium bromide solution takes one of two paths. One
path has the lithium-bromide solution flowing down to the absorber,
being mixed with higher concentrated lithium-bromide solution coming
from the high temperature generator/concentrator, heated, and
discharged into absorber. The other path has the lithium-bromide
solution being heated and pumped to the high temperature
generator/concentrator where steam, hot water, or direct-fired
heating is applied to raise the lithium bromide solution to a
temperature where the liquid refrigerant vaporizes and travels to the
condenser. The highly concentrated lithium bromide solution is mixed
with the concentrated lithium bromide going to the absorber.
Chiller Performance Standard
|
|
| Diagram 1. Single-effect Duhring diagram. |
|
The
primary absorption chiller performance standard is ARI Standard 560
(2000 Standard for Absorption Water Chilling and Water Heating
Packages). ARI Standard 560 applies to water cooled single-effect
steam chillers, water cooled single-effect hot water chillers, water
cooled double-effect steam chillers, water cooled double-effect hot
water chillers, and water cooled double-effect direct-fired chillers.
This standard provides testing standard conditions, rating
requirements, minimum data requirements for published ratings, and
integrated part load value (IPLV) or non-standard part load value
(NPLV). For performing the IPLV testing, ARI
Standard 560 has established standard conditions for absorption
chillers including:
- Entering condenser water temperature: 85°
- Condenser water flow rate: 3.6 gpm/ton (single-effect indirect
fired)
- 4.0 gpm/ton (double-effect
indirect fired, double-effect direct-fired)
- Condenser water-side fouling factor: 0.00025
- Evaporator leaving water temperature: 44°
- Evaporator water flow rate: 2.4 gpm/ton
- Evaporator waterside fouling factor: 0.0001
- Tube-side fouling factor (steam): 0.000 (indirect
fired)
- Tube-side fouling factor (hot
water): 0.0001 (indirect fired)
It
is very important to understand that chillers rarely operate at their
maximum capacity. ARI used typical building types and operations in
29 different cities to develop a chiller loading profile during a
typical year. The resulting chiller loading profile is at 100%
capacity about 1% of the time, 75% capacity about 42% of the time,
50% capacity about 45% of the time, and 25% capacity about 12% of the
time. These values are incorporated into the IPLV equations, which
are:
|
|
| GRAPH 1. Chiller part-load energy usage. |
|
IPLV
= 0.01A + 0.42B + 0.45C + 0.12D (coefficient
of performance [COP]) where: A
= COP at 100% capacity (condenser water at 85° ) B
= COP at 75% capacity (condenser water at 77.5° ) C
= COP at 50% capacity (condenser water at 70°) D
= COP at 25% capacity (condenser water at 70°)
IPLV
= 1
(MBtuh/ton) where: (0.01/A) + (0.42/B) +
(0.45/C) + (0.12/D)
A
= MBtuh/ton at 100% capacity (condenser water at 85° ) B
= MBtuh/ton at 75% capacity (condenser water at 77.5°) C
= MBtuh/ton at 50% capacity (condenser water at 70°) D
= MBtuh/ton at 25% capacity (condenser water at 70°)
|
|
| GRAPH 2. Chiller capacity vs. condenser entering water temperature. |
|
When
evaluating different chiller energy usage, the IPLV provides the most
accurate average chiller energy usage. When the known parameters are
different than prescribed above, the part-load performance becomes
NPLV which has the same equation as the IPLV. Ultimately, the
chiller’s energy usage is primarily based upon the “lift” or
temperature difference between the chilled water leaving temperature
and condenser water leaving temperature. Lowering the condenser water
leaving temperature or raising the chilled water leaving temperature
will reduce lift and energy usage of chiller, but not necessarily
chilled water system. Raising the condenser water leaving temperature
or lowering the chilled water leaving temperature will increase lift
and energy usage of chiller.
Chiller Operating Performance
As
with motor-driven vapor compression chillers, absorption chillers do
not operate at the standard operating conditions noted above. Though
there are many variables that can be evaluated; for this article,
absorption chiller COP vs. part -load percentage and chilled water
leaving temperature vs. chiller capacity shall be evaluated. Note
that the graphs are illustrative only. It is important that you use
the particular chiller performance data for the equipment you are
evaluating.
Effect
of part-load operation on chiller efficiency. Looking at
Graph 1, all three types of absorption chillers are most efficient at
50% part load with the single-effect indirect-fired chiller having a
9.4% increase in efficiency; the double-effect direct-fired chiller
having a 10% increase in efficiency; and the double-effect
indirect-fired chiller having a 16.7% increase in efficiency. At part
loads below 50%, the chiller efficiencies are lower as the chiller
part load is lower.
Effect
of chilled water leaving temperature. The standard chilled
water leaving temperature is 44°. Looking at Graph 2, chiller
capacity increases as the chilled water leaving temperature
increases. At a chilled water leaving temperature of 48°, the
chiller capacity increased 8% for single-effect absorption chiller
and increased 9.5% for double-effect absorption chiller as compared
to chilled water leaving temperature of 44°.
Conversely,
the chiller capacity decreases as the chilled water leaving
temperature decreases. At a chilled water leaving temperature of 40°,
the chiller capacity decreased 14.5% for single-effect chiller and
decreased 11.4% for double-effect absorption chiller as compared to
chilled water leaving temperature of 44°.
Aborption Chillers And LEED®
The
USGBC LEED for New Construction, Version 2.2, has a mandatory
prerequisite to reduce ozone depletion by utilizing no CFC
refrigerants in new construction and phasing out CFC refrigerants
during renovation of existing facilities. Since the two frequently
used absorption chiller refrigerants are ammonia and water,
absorption chillers meet the Energy & Atmosphere Prerequisite 3,
Fundamental Refrigerant Management, requirement of no CFC
refrigerants.
The USGBC also provides the
opportunity for obtaining a credit for Enhanced Refrigerant
Management. Understanding some lower ozone-depleting refrigerants are
also less efficient, the Energy & Atmosphere Credit 4, Enhanced
Refrigerant Management has developed a formula that weighs a
refrigerant’s ozone depletion and global warming potentials. If the
project’s total installed refrigerant has an average atmospheric
impact less than a 100, it is eligible for the credit (See USGBC for
further information on formula).
The credit
also recognizes “natural refrigerants” like water, carbon
dioxide, ammonia, and propane as having a lower atmospheric damage
potential and will allow projects exclusively using natural
refrigerants to claim the credit without using the Enhanced
Refrigerant Management formula. Absorption chillers can be a key
component in meeting the USGBC strategy of reducing atmospheric
damage.
Absorption Chiller Energy Efficiency
Absorption
chiller energy efficiency is based upon fuel consumption per ton
cooling while motor driven vapor compression chiller energy
efficiency is based upon kW/ton cooling. The COP is a method for
determining overall chiller energy performance.
For
absorption chillers, the COP formula is:
COP
= Eu
/ Ea
where: Eu
= useful energy obtained (Btuh)
Ea
= energy used (Btuh)
For
motor-driven chillers, the COP formula is:
COP
= 12 KW/ton
x 3.412
Per manufacturer supplied information,
the coefficient of performance range for the different absorption
chiller types are as follows:
Absorption
chiller type COP range
Hot
water or steam single-effect chiller..............0.60 to
0.75
Hot water or steam double-effect
chiller.............1.19 to 1.35
Direct fired
double-effect chiller.......................................1.07 to
1.18
Looking at the COP ranges, the
single-effect chiller is the least energy-efficient absorption
chiller type with the hot water, steam, and direct-fired,
double-effect absorption chillers being almost twice as energy
efficient. The hot water and steam double-effect absorption chillers
are the most energy efficient absorption chillers, but how do they
compare to motor driven vapor compression chillers?
The
two motor-driven vapor compression chillers being utilized for energy
efficiency comparison are the water cooled rotary screw chiller and
the water cooled centrifugal chiller. Per manufacturer supplied
information, the water cooled rotary screw chiller has a COP range of
3.90 to 5.40 while the water cooled centrifugal chiller has a COP
range of 7.00 to 8.79. The result is that motor driven vapor
compression chillers are 4 to 7 times more energy efficient than
absorption chillers. This leads to a question: Why would you want to
use an absorption chiller?
Advantages Of Using Absorption Chillers
In
an energy-efficiency competition, motor-driven vapor compression
chillers will beat absorption chillers every time. However, there are
specific applications where absorption chillers have a substantial
advantage over motor-driven vapor compression chillers. Some of those
applications include:
- For a facility that has a cogeneration power plant or other thermal
energy generating process with excess thermal energy, absorption
chillers can utilize this excess thermal energy to produce chilled
water instead of all the excess thermal energy being
wasted.
- For a facility that has
inadequate electrical infrastructure or bringing electrical
infrastructure to the facility is cost prohibitive, absorption
chillers have a substantially lower electrical power requirement than
motor driven vapor compression chillers.
- For a facility with high electrical power cost and low fuel cost,
absorption chillers may have a lower operating cost than motor driven
vapor compression chillers.
- For a
facility that requires substantial system reliability, the lower
electrical requirements for absorption chillers will reduce emergency
generator load requirements.
- For a
facility that has high electrical demand charges, absorption chillers
can be used as part of a peak shaving strategy.
- For a facility that has very low acoustical and/or vibration
requirements, absorption chillers have lower noise and vibration
generation than motor driven vapor compression chillers.
- For a facility wanting to use a “natural refrigerant,”
absorption chillers are a good choice.
Summary
The
future for absorption chillers is bright. With power utilities
increasing electrical demand charges during peak hours as a strategy
to delay building new power generating stations, absorption chillers
can be the corner stone for an electrical demand limit strategy. With
absorption chillers using “natural refrigerants,” they will
become more attractive as more restrictions are placed on HCFC and
other refrigerants. With the improved lithium bromide solution
concentration control, absorption chillers are more reliable. ES
|