Basics For Refrigerant Chillers
by Vincent A. Sakraida, P.E.
December 1, 2008
|
|
| Figure
1. Water cooled chiller
diagram. |
|
That
pretty much covers it. You know, design options, performance
standards, part-load values, operating factors, and more. Use it
as a quick brush-up, or pass it along as a handy reference.
With
over 80,000 operating units in North America, chillers are the
cooling workhorses for many commercial and industrial facilities.
There are two primary chiller types: absorption and refrigerant,
which operate very differently. This article will focus on
refrigerant chillers.That
pretty much covers it. You know, design options, performance
standards, part-load values, operating factors, and more. Use it
as a quick brush-up, or pass it along as a handy reference.
There
are two primary types of refrigerant chillers, either air cooled and
water cooled condenser with either scroll, screw, or centrifugal
compressors. Also, a number of design variables affect chiller
design, selection, and performance, including chilled water supply
and return temperatures, percentage of chilled water glycol,
condenser water supply and return temperatures, refrigerant-type
used, chilled water system part-load requirements, chiller
installation altitude, sequence of operation requirements, and
available electrical service. These and other factors make
refrigerant chillers the most complex piece of HVAC equipment.
This article’s goal is to provide the
reader with a basic refrigerant chiller description, applicable
chiller performance standard, normal operating parameters, and
information on chiller operation outside of normal operating
parameters.
Refrigerant Chiller Description
Refrigerant
chillers follow the Carnot Cycle, which has four main steps (Figure
1): compression (compressor), condensing (condenser), expansion
(expansion valve), and evaporation (evaporator). Note the chiller has
a high-pressure side (from compressor through condenser to expansion
valve) and low-pressure side (from expansion valve through evaporator
to compressor).
Most scroll and screw
chillers have available options but are not considered custom-made
machines, while centrifugal chillers are typically custom-designed
and built, giving the designer substantial flexibility. The following
component descriptions will include some available options and
standard operating parameters:
Evaporator.
The evaporator is
where the refrigerant removes heat (energy) from the chilled water.
The evaporator can be a brazed-plate-frame heat exchanger (smaller
scroll and screw chillers) or a shell-and-tube heat exchanger. The
two shell-and-tube evaporator types include DX barrel (refrigerant
runs through tubes and water runs through shell) and flooded (water
runs through tubes and refrigerant runs through shells).
To
ensure good heat transfer between the chilled water and refrigerant,
it is important to maintain turbulent chilled water flow. The
recommended minimum chilled water flow velocity is 3 feet per second
(fps) to prevent laminar flow, and the maximum chilled water flow
velocity is 12 fps to prevent pipe erosion. Evaporators come in one,
two, or three passes configurations with the number of passes being
dependent upon chilled water temperature difference and
manufacturer’s standard product (Figure 2).
|
|
| Graph
1. Part load energy usage. |
|
Typically,
a single-pass evaporator heat exchanger is adequate for chilled water
entering/leaving temperature differentials up to 6°F, a two-pass
evaporator heat exchanger is adequate for chilled water
entering/leaving temperature differentials of between 6° and 12°,
and a three-pass evaporator heat exchanger is adequate for chilled
water entering/leaving temperature differentials of between 12°
and 18°. Note: Manufacturers may configure their heat exchangers
differently to reduce the number of passes for higher temperature
differences. With design chilled water entering/leaving temperature
differentials increasing from 10° to 16° or 18° to reduce
pipe sizes and pumping energy, newer chiller evaporator heat
exchangers may be larger. Condenser.
The condenser is where
the refrigerant rejects heat (energy) to the condenser water or air,
causing refrigerant phase change from gas to liquid. There are three
condenser types: water cooled, air cooled, and evaporative cooled.
Most chillers utilize water cooled or air cooled condensers, and
these two condensers are discussed.
- Water
cooled condenser. Water
cooled condensers typically involve a shell-and-tube heat exchanger
with condenser water running through the tubes and the refrigerant in
the shell space. The condenser water flow must have the same flow
velocity range as the evaporator, 3 fps to 12 fps. Water cooled
condensers come in one-, two-, or three-pass configurations with
similar water entering/leaving temperature differentials as chilled
water. A standard water cooled condenser is rated at 85° ambient
outdoor air temperature but performance data is usually provided for
65° and 75° ambient outside air
temperature.
- Air
cooled condenser.
The air cooled condenser is where the refrigerant rejects heat
(energy) directly to the outside air. Air cooled condensers can be an
integral chiller component or be a remote condenser with refrigerant
piping connecting it to the chiller. The air cooled condenser is a
coil(s) having copper tubing with aluminum fins and condenser fan(s).
A standard air cooled condenser is rated at 95° ambient outside
air temperature, but performance data is usually provided for 105°
and 115° ambient outside air temperature.
Compressor.
The compressor is the
chiller system’s heart. It takes the lower-pressure vaporized
refrigerant coming out of the evaporator, compresses it to a higher
pressure, and discharges it into the condenser. Chiller systems
utilize two types of compressors, positive-displacement and dynamic.
Positive-displacement compressors physically compress the vaporized
refrigerant into a smaller volume and higher pressure, and include
reciprocating, rotary, and orbital types. The two most utilized
positive-displacement compressors are the scroll and rotary screw. A
centrifugal compressor is the most utilized dynamic compressor.
Dynamic compressors increase vaporized refrigerant pressure by the
kinetic energy imparted on refrigerant by a rotating impeller.
Each compressor type’s method of operation,
advantages, available chiller capacities, and energy usage range are
as follows:
- Scroll
compressor. The
scroll compressor is a positive displacement machine that consists of
two interleaved scrolls (Figure 3). One scroll is stationary while
the other scroll orbits eccentrically, compressing the refrigerant.
The scroll compressor’s advantages include fewer moving parts,
quieter operation, and compact size. The scroll compressor’s
high-tolerance machining requirement limits the scroll cooling
capacity to 30 tons or less. Air cooled scroll chillers are available
with cooling capacities between 10 tons and 190 tons and energy usage
between 1.1 and 1.5 kW/ton. Water cooled scroll chillers are
available with cooling capacities between 30 tons and 120 tons and
energy usage of 0.7 and 0.9 kW/ton.
- Rotary
screw compressor. The
rotary screw compressor is a positive displacement machine that
consists of either a single or twin screw(s) (Figure 4). The screw(s)
rotate to compress the refrigerant into a smaller volume, raising its
pressure. Screw compressor advantages include higher reliability,
compact size, and tighter chilled water temperature control (+0.5°F).
An individual screw compressor has a cooling capacity of 200 tons or
less. Air cooled screw chillers are available with cooling capacities
between 80 tons and 500 tons and energy usage between 1.1 and 1.5
kW/ton. Water cooled screw chillers are available with cooling
capacities between 70 tons and 265 tons and energy usage between 0.65
and 0.9 kW/ton.
- Centrifugal
compressor. The
centrifugal compressor is a dynamic machine that includes an impeller
(Figure 5). The spinning impeller transfers its kinetic energy to the
refrigerant, raising the vaporized refrigerant’s pressure. The
critical variable for centrifugal compressors is the impeller tip
speed, which must be maintained regardless of chiller loading.
Centrifugal compressor advantages include larger capacity chillers,
lower energy usage, multi-stage compression, and higher reliability.
An individualcentrifugal compressor has a cooling capacity of
2,000 tons or less.
Centrifugal chillers are
water cooled and are available with cooling capacities of 200 tons to
2,000 tons for a single-compressor centrifugal chiller, and 400 tons
to 4,000 tons for a two-compressor centrifugal chiller. Centrifugal
compressor chillers are the most energy efficient chillers with
energy usage between 0.5 and 0.6 kW/ton.
- Expansion
valves.
High-pressure liquid refrigerant passes through expansion valves,
reducing pressure and flashing to a gas within the evaporator,
absorbing energy from the chilled water. Expansion valves range from
a simple orifice opening in the pipe to a complex modulating valve
that provides dynamic load control.
- Refrigerants.
Refrigerant technology is changing because production of
several commonly used refrigerants will soon end, including R-22 in
2010 and R-123 in 2020. However, refrigerants should be available for
the life of R-22 and R-123 chillers purchased today.
Refrigerants come in three classifications:
high pressure (R-22, R-407C, and R-410A), medium pressure (R-134A),
and low pressure (R-123). The high-pressure and medium-pressure
refrigerants are utilized in positive-displacement chillers, and the
medium- and low-pressure refrigerants are used for dynamic chillers.
Scroll chillers typically use R-22, R-407C, or R-410A refrigerants.
Screw chillers typically use R-134A or R-407C refrigerants.
Centrifugal chillers typically use R-123 or R-134A refrigerants.
Chiller Performance Standard
|
|
| Graph
2. Chiller capacity vs. condenser entering water temperature. |
|
ARI
Standard 550/590 is the primary performance standard for screw and
centrifugal chillers up to 2,000 tons, though many manufacturers
interviewed for this article utilized ARI Standard 550/590 for rating
their water cooled scroll chillers, air cooled scroll chillers, and
air cooled screw chillers. This standard provides a testing protocol
for determining the chiller capacity (tons), energy usage (kW/ton),
fluid pressure drop (ft of water), and integrated part load value
(IPLV) or non-standard part load value (NPLV). The
standard has established testing criteria for performing the testing,
including:
|
|
| Graph
3. Chiller energy usage vs. condenser entering water temperature. |
|
- Leaving
chilled water temperature: 44°
- Evaporator
waterside fouling allowance: 0.0001
- Chilled
water flow rate: 2.4 gpm/ton
- Entering
condenser water temperature: 85°
- Condenser
waterside fouling allowance: 0.00025
- Condenser
water flow rate: 3.0 gpm/ton
It
is very important to understand that chillers rarely operate at their
maximum capacity. Studies were performed to determine actual chiller
loading during a typical year, where the results found a chiller is
at 100% capacity about 1% of the time, 75% capacity about 42% of the
time, 50% capacity about 45% of the time, and 25% capacity about 12%
of the time (See graph 1 for kW/ton vs. percent of part load for
typical scroll, screw, and centrifugal chillers). These values were
incorporated into IPLV equation, which is:
|
|
| Graph
4. Chiller capacity vs. chilled water temperature difference. |
|
IPLV
= 0.01A + 0.42B + 0.45C + 0.12D where: A =
kW/ton at 100% capacity (condenser water at 85°) B
= kW/ton at 75% capacity (condenser water at 75°) C
= kW/ton at 50% capacity (condenser water at 65°) D
= kW/ton at 25% capacity (condenser water at
65°) When
evaluating different chiller energy usage, the IPLV provides the most
accurate average chiller energy usage. When the known parameters are
different than prescribed above, the part-load performance becomes
NPLV, which is described using the same equation. Ultimately, the
chiller’s energy usage is primarily based upon the “lift” or
temperature difference between the chilled water leaving temperature
and condenser water leaving temperature. Lowering
the condenser water leaving temperature or raising the chilled water
leaving temperature will reduce lift and energy usage for chillers
but not necessarily the chilled water system. Raising the condenser
water leaving temperature or lowering the chilled water leaving
temperature will increase lift and energy usage for chillers but not
necessarily the chilled water system. Varying a number of chiller
variables and the resulting impact on chiller capacity and energy
usage will be discussed.
Chiller Operating Performance
Most
chillers do not operate at the standard operating conditions noted
above. As noted in the introduction, there are many variables that
affect chiller operation. Below, this article investigates the effect
of modifying three chiller variables (condenser water temperature,
chilled water temperature difference, chilled water leaving
temperature) on chiller operations. Note the graphs are illustrative
only. Always use the particular chiller performance data when
evaluating a chiller. Because centrifugal chillers are custom-made,
data were not available for all variables being
discussed.
Effect
of condenser water temperature changes.
The standard chiller condenser water temperature is 85°. Looking
at graph 2, chiller capacity increases as the condenser water
temperature decreases. At a condenser water temperature of 75°,
scroll chiller capacity increased 4.9%, screw chiller capacity
increased 5.6%, and centrifugal chiller capacity increased 10% as
compared to condenser water at 85°.
Conversely,
chiller capacity decreases as the condenser water temperature
increases. At a condenser water temperature of 95°,
scroll-chiller capacity decreased 4.4%, screw chiller capacity
decreased 6.1%, and centrifugal chiller capacity decreased 10% as
compared to condenser water at 85°.
Looking
at graph 3, the chiller’s energy usage reduces as the condenser
water temperature decreases. At a condenser water temperature of 75°,
screw chiller energy usage decreased 18% and centrifugal chiller
energy usage decreased 11% as compared to condenser water at 85°.
Conversely,
the chiller energy usage increases as the condenser water temperature
increases. At a condenser water temperature of 95°, screw-chiller
energy usage increased 21%, and centrifugal chiller energy usage
increased 19% as compared to condenser water at 85°.
Effect
of chilled water temperature difference.
The standard chilled water temperature difference is 10°. Looking
at graph 4, the chiller capacity increases as the chilled water
temperature difference increases. At a chilled water temperature
difference of 16°, the scroll and screw chiller capacity
increases 2.1% as compared to chilled water difference of 10°.
Conversely,
the chiller capacity decreases as the chilled water temperature
difference decreases. At a chilled water temperature difference of
6°, the scroll and screw chiller capacity decreases 1.4% as
compared to chilled water difference of 10°.
Looking
at graph 5, the chiller’s energy usage increases as the chilled
water temperature difference increases. At a chilled water
temperature difference of 16°, the scroll and screw chiller
energy usage increased less than 1% as compared to chilled water
difference of 10°.
Conversely,
the chiller’s energy usage reduces as the chilled water temperature
difference decreases. At a chilled water temperature difference of
6°, chiller energy usage decreased less than 1% as compared to
chilled water difference of 10°. This analysis is based on
keeping the chilled water supply temperature at 44°.
Effect
of chilled water leaving temperature.
The standard chilled water leaving temperature is 44°. Looking at
graph 6, chiller capacity increases as the chilled water leaving
temperature increases (graph 4). At a chilled water leaving
temperature of 50°, the chiller capacity increased 12.8% for
water cooled screw chiller and increased 34.7% for air cooled screw
chiller as compared to chilled water leaving temperature of 44°.
Conversely,
the chiller capacity decreases as the chilled water leaving
temperature decreases. At a chilled water leaving temperature of 40°,
the chiller capacity decreased 7.2% for water cooled screw chiller
and decreased 19.8% for an air cooled screw chiller as compared to a
chilled water leaving temperature of 44°.
Looking
at graph 7, chiller energy
usage decreases as the chilled water leaving temperature increases.
At a chilled water leaving temperature of 50°, the chiller energy
usage decreased 12% for the water cooled screw chiller and decreased
10.7% for an air cooled screw chiller, as compared to chilled water
leaving temperature of 44°.
Conversely,
chiller energy usage increases as the chilled water leaving
temperature decreases. At a chilled water leaving temperature of 40°,
the chiller’s energy usage increased 13% for the water cooled screw
chiller and 8.1% for the air cooled screw chiller as compared to
chilled water leaving temperature of 44°.
Summary
This
article provided basic chiller component descriptions. It is
important to note there are many additional chiller components and
subsystems that were not discussed but require careful consideration
during the design/selection process. A chiller selection analysis was
not included due to site-specific limitations and requirements having
a substanital impact on final chiller selection. Chiller selection
analysis deserves to be a standalone article. Finally, it is
important to understand the affect changing chiller operating
parameters from the ARI Standard has on chiller operating performance
with the following being noted:
- It
is important to use the IPLV for selecting a chiller with the best
energy usage.
- Modifying condenser
water entering temperature has a higher impact on chiller energy than
chiller capacity does.
- Modifying
chilled water leaving/return temperature difference has a higher
impact on chiller capacity than chiller energy usage, when chilled
water leaving temperature remains constant.
- Modifying
chilled water leaving temperature has a substantial impact on chiller
capacity and chiller energy usage. ES
|