|
|
Manufacturing The Right Moisture
by Vincent A. Sakraida, P.E.
April 1, 2007
|
|
|
Figure 1.
Psychrometric chart. (Courtesy of Bry-Air, Inc.)
|
|
In addition to serving as a handy reference on the various
dehumidification technologies and their profiles, this article uses a
manufacturing scenario to explore load-related questions and other design
pitfalls. Will human occupancy make much of a difference? What valves does your
humidifier have? And exactly what’s in that room, anyway?
The reasons for controlling rh include prevention of mold
growth/condensation, product/artifact life extension, product quality
improvement, prevention of moisture re-entrainment, static electricity control,
and human comfort. In fact, many of today’s manufacturing processes would not
be feasible without dehumidification. This article provides a brief discussion
on recommended relative humidities, available dehumidification technologies,
moisture load sources, and dehumidification pitfalls that can cause problems
with your dehumidification systems.
Recommended Rh
The obvious source for finding recommended rh levels is
ASHRAE, however, many other organizations have performed or funded studies on
the influence rh has in their particular industries. One study was performed to
determine how much weight potatoes lose being stored over time at relative
humidities below the optimum storage rh (95%) and the financial impact to the
farmer. Other studies have looked at the effect rh has on the storage of
archived material (parchment, film, paper). The organizations performing these
studies do not always draw the same conclusions for the same application. In
light of this fact, the following recommended relative humidities (Table 1),
with corresponding temperatures, should be viewed as being general in nature.
It is strongly suggested that the design professional research available
studies and consult industry experts to determine the best rh for their
specific situation.
Dehumidification Technologies
|
|
|
Figure 2. Solid
desiccant wheel schematic. (Courtesy of Munters Dehumidification Division.)
|
|
Dehumidifying air can be achieved by utilizing technologies
that take advantage of particular air properties. The moisture can be squeezed
out, chilled out, adsorbed out, absorbed out, or a combination of these
technologies. A description on how each technology dehumidifies, and its
limitations, follows.
Squeezed out. The higher the air
pressure, the less moisture air can retain. A good example is an air compressor.
When air is compressed from atmospheric to 100 psig in an air compressor, water
condenses out in the air receiver and is removed by a drain valve. Compression
is not a very efficient method of moisture removal and will not be discussed
further.
Chilled out. The lower the air
temperature, the less moisture air can retain. Moisture can be removed from the
air by cooling it below its dewpoint temperature. For example, if air entering
a cooling coil is 80°F, 50% rh, the air would need to be cooled below its
dewpoint of 60.5° in order to start removing moisture from the airstream
(Figure 1). Cooling coils have the capability to provide adequate
dehumidification for most applications with a dewpoint requirement of 38° or
higher. Cooling coils can be DX, chilled water, or glycol/brine water type. The
limitations of each coil type are as follows.
- DX coil – Refrigerant coils can
cool air to extremely low temperatures, but cooling the air below 32° would
cause ice/frost to freeze on the coil, clogging it. Also, the refrigerant
expansion within the coil is not necessarily uniform, resulting in an uneven
temperature gradient across the coil. To prevent potential frost/ice build-up
on the DX coil, the lowest leaving air temperature should be 38° to 40°
- Chilled water coil – Chilled
water coils are typically served by a central chilled water system, which
supplies chilled water at 40° to 45°. The water/air coil approach temperature
is typically 3° to 5°, resulting in a minimum leaving air temperature of
45° to 50° .
- Brine/glycol coil –
Brine/glycol coils are typically served by a dedicated chilled water system to
serve that specific coil or group of coils. A brine/glycol-chilled water system
can supply water at very low temperatures. As with the DX coil, lowering the
air temperature below 32° will cause ice/frost build-up on the coil. However,
the advantage of the brine/glycol coil over the DX coil is the brine/glycol
coil has an even temperature gradient across the coil, making it possible to
have a leaving air temperature of 35° without developing ice/frost on the coil.
Adsorbed out. Desiccants are substances that readily capture
water vapor. There are two primary types of desiccants, adsorbents and
absorbents. Adsorbents work like a sponge holding the moisture on the surface
and in the pores of the desiccant. The desiccant materials used include silica
gel, activated alumina, and molecular sieve. The silica gel desiccant is the
most frequently used. For applications having dewpoints down to
-30°, the silica gel and activated alumina are good selections. For
applications below -30°, the molecular sieve would be a good selection. Discuss
the best desiccant material with your desiccant system manufacturer to
determine the optimum selection for your particular application.
It is important to note that low dewpoint applications will
use purged air that takes low dewpoint process air and uses it for
regeneration. The typical adsorption desiccant system consists of a wheel
impregnated with the desiccant. The wheel rotates and the airstream passes
through the wheel, removing the moisture from the airstream. The wheel rotates
into a regeneration section where heated air is blown across the wheel to
remove the moisture (Figure 2). The advantage of the adsorption desiccant
system is the wheel will not sustain moisture overload when turned off. Due to
the adsorption type desiccant system having simpler operation and maintenance,
it is the most popularly used desiccant system.
Absorbed out. The other type of
desiccant is an absorbent. Absorbents can be solids or liquids, and undergo a
chemical change as they absorb moisture. Two chemicals frequently used in
desiccant absorption type dehumidifiers are lithium chloride and sodium
chloride. Of the two absorption desiccants, lithium chloride is utilized the
most. Lithium chloride systems can provide good performance for dewpoints down
to -20° and typically use 10% less energy than silica gel adsorption systems.
Absorption dehumidifiers come in liquid or solid types with a description of
each type as follows:
- Liquid type – The liquid type
has the conditioner where the air flows up through packing while the liquid desiccant
is sprayed down on the packing. The lithium chloride will absorb the moisture
out of the air and drop to a sump at the bottom of the conditioner (Figure 3).
The moisture laden lithium chloride is pumped to a regenerator where it is
heated and the moisture is removed. Once the moisture is removed, the lithium
chloride returns to the conditioner, cooled and ready to absorb more moisture,
repeating the cycle. The liquid system’s disadvantages are potential corrosion
from lithium chloride carryover in the air supply system and higher maintenance
costs. In recent years, technological advancements have reduced the potential
of lithium chloride carryover.
- Dry
type – Like the adsorption units, the absorption units have a
rotating wheel configuration. Unlike the adsorption type desiccant wheels, care
must be taken when the absorption desiccant wheel is running. If process or reactivation
air is allowed to run through the desiccant wheel without the reactivation
heater enabled, the desiccant wheel can be damaged. Controls to prevent this
from occurring are standard for this type of equipment.
Chilled out/adsorbed out combination. Often
the most energy efficient dehumidification system uses both chilling and
desiccant technologies together. Chilling is used first to reduce temperature
and moisture where this technology operates most efficiently on hot airstreams.
Desiccants are then used to further dry the air to the required levels to
maintain humidity setpoints. Technologies are available that utilize condenser
and compressor waste heat for reactivation as are internal purges that reduce
reactivation and cooling energy. Discuss these alternatives with manufacturers
to determine the most energy efficient type of system for your application.
Moisture Load Sources
|
|
|
Figure 3. Liquid
desiccant system schematic. (Courtesy of AIL Research, Inc.)
|
|
Moisture load calculations are important in determining how
much moisture must be removed in order to maintain the specified space humidity
conditions. Take caution when performing these calculations, as moisture
sources are not always obvious.
A fictitious manufacturing building will serve as a case
example for individual moisture source order of magnitude loads. The example is
as follows.
- The building is 100- x 500- x 50-ft high
with a 100- x 300-ft conditioned area.
- The walls are 8-in. concrete masonry units (CMU)
with no vapor barrier, the floors are 6 in. concrete with no vapor barrier, and
the roof is built-up over metal decking.
- Each of the
seven main doors (3 ft x 7 ft) open one minute per hour.
- One overhead door (10 ft x 16 ft), between
conditioned and unconditioned space, is open one minute per hour.
- The outside air is 93° db, 80° mean wb, 135
grains/lb air, 75.5° dewpoint, and vapor pressure (VP) is 0.875.
- Inside air is 75° db, 20% rh, 26 grains/lb air,
32° dewpoint, VP is 0.180.
- An outside wind speed of 15 mph is assumed.
- Seven people work in the conditioned space: two
sitting at desk, and five performing light work.
- Manufacturing material is plastic with a process
through-put of 10,000 lb/hr.
- The manufacturing floor is washed down in 300 sq
ft areas every hour with 100° hot water. Fans are used to shorten the
evaporation time and flow parallel to floor at 300 fpm.
- The
manufacturing process produces 100 cu ft of unvented natural gas per hour.
- There are no air openings except the doors.
- 15,000 cfm of outside air is brought into the building
to provide positive space pressurization.
The most prevalent
building moisture load sources and the variables that affect the amount of
moisture load they contribute are as follows:
-
Permeation moisture – Building walls and floors
typically allow moisture migration from the higher vapor pressure to the lower
vapor pressure environment, even when vapor barriers are used. The variables affecting
permeation moisture load are material of construction permeance, wall and floor
square footage, and vapor pressure differential across material of
construction. Looking at the example, the building wall moisture load is 9.5
lb/hr with no vapor barrier. Though 9.5 lb/hr is not a substantial portion of
the total space moisture load, it can be significant enough to cause problems.
Painting the CMU blocks with a vapor retardant paint will reduce the wall
moisture load by 84% to 1.50 lb/hr.
-
-
Product and packaging – Most materials are hygroscopic (affinity to
absorb moisture). When a moisture-containing material is placed in an
environment having a lower rh, it will de-sorb its moisture into the
environment. In our examples, the outside air has an rh of 55% with the inside
having a 20% rh. The variables affecting product/packaging moisture load are
product moisture content, product entry weight, product de-sorption rate, and
rh differential. Looking at the example, the product moisture load is 500
lb/hr. It is important to know the anticipated maximum process material
through-put. It might be necessary to pre-dry the material before bringing it
into the facility.
-
-
Personnel – Human beings give off
moisture through breathing and perspiration. The variables affecting personnel
moisture load are space temperature, level of physical activity, and number of
people. Looking at the example, the manufacturing building has a personnel
moisture load of 2.7 lb/hr. Though the personnel load is low in this example,
it can be a major moisture load contributor in high occupation density areas
like schools, arenas, and airports.
-
-
Combustion – One of the byproducts of combustion is water
vapor. Looking at our example, the manufacturing combustion moisture load is
9.3 lb/hr. Make sure you take into account any combustion moisture removed from
the space by an exhaust stack.
-
-
Wet surface evaporation – Any wet surface exposed
directly to the environment will evaporate, adding to the moisture load. The
variables affecting wet surface moisture load are wet surface area, vapor
pressure at water temperature, vapor pressure at air temperature, and air
velocity and direction blowing on the water. Water that is 50° with no air
movement will take longer to evaporate than water that is 140° with transverse
air velocity of 300 fpm. Looking at the example, the water surface evaporation
moisture load is 115.5 lb/hr.
-
-
Air infiltration – The amount of air infiltration a building will
experience is based upon material of construction, quality of construction,
building surface to area ratio, and average wind speed. Buildings tend to have
substantial leakage through door cracks, doors opening and closing, wall
seams/joints/cracks, wall penetrations, and any other crack that will allow
moisture laden air to leak into the building. The variables affecting air
infiltration are hole opening area, air velocity through opening, air density,
and moisture differential between outside and inside air. Looking at the
example, air leakage coming into the building is reduced due to positive air
pressurization within the building. However, there will be air leakage when
doors are opened and closed. The resulting air leakage moisture load is 149.1
lb/hr. If the personnel doors have air locks installed, the air leakage is
reduced to 10.6 lb/hr, a 93% reduction in moisture load.
-
-
Ventilation – Most buildings will bring in outside
air to replace exhausted air, maintain IAQ, and provide building
pressurization. Providing enough ventilation to positively pressurize the
building will reduce uncontrolled air leakage into the building. Looking at the
example, the ventilation moisture load is 976.6 lb/hr. Ventilation moisture
loads tend to be one of the highest moisture loads that need to be mitigated.
In summary, ventilation and air infiltration tend to be the
higher moisture load sources. Using air locks and making spaces as air tight as
possible can substantially reduce air infiltration loads. Using a vapor barrier
can substantially reduce building permeation moisture load. Building occupancy,
process material, and combustion moisture loads have the potential to be substantial.
Dehumidification Pitfalls
|
|
|
Table 1. Recommended
rh levels for typical applications.
|
|
It is more difficult to
maintain a specific rh than a specific temperature, resulting in it being
easier to lose humidity control. The following are specific problems that need
to be understood and accounted for.
Wrong calculations. When performing cooling load calculations, it is
typical to use the 0.4% design condition drybulb temperature with mean
coincident wetbulb temperature. By using this weather data, are we assured the
maximum total and latent load is calculated? The answer is no. There is a good
probability that a warm, rainy afternoon will produce a substantially higher
latent and total cooling load. The result will be that the system will not be
able to maintain the space design rh. It is important to calculate the cooling
load at the maximum outside air dewpoint temperature with coincident drybulb
temperature. ASHRAE Handbook – Fundamentals provides the maximum outside air dewpoint
temperature with coincident drybulb temperature.
Wheel temperature rating. Do you know the maximum temperature rating for
the desiccant wheel you are using? How is the desiccant wheel being regenerated
(steam/natural gas)? Is there a potential the desiccant wheel will be
overheated, and what damage would result? An overheated desiccant wheel can
warp or deform, requiring replacement.
Space pressurization. As noted above, reducing moist air infiltration
into a controlled space to a minimum is necessary to provide adequate rh
control. Spaces having neutral or negative space pressurization in relation to
surrounding spaces and/or outside environment will be very difficult to
maintain at a set rh, especially spaces requiring very low rh.
Building envelope integrity. Reducing moisture migration through building
walls and floors to a minimum is necessary to provide adequate rh control. Some
facilities cannot maintain a set rh due to walls and floors having high
permeance rates. Also, reducing uncontrolled moisture migration through cracks
and around penetrations is extremely important. Sealing is a good deal.
Humidification operation. Is your humidifier operation locked out during
dehumidification operation? Does your humidifier have a two-position valve as
well as a modulating valve to prevent humidifier leakage?
Final Thoughts
A properly designed facility, both architecturally and
mechanically, can provide a stable rh environment. This article tried to give
an appreciation for the complex variables that affect dehumidification design
and operation. Going forward, do the following steps:
- Know the required temperature and rh set points,
including allowable humidity rate of change.
- Know the
architectural layout and design. Work with the architect to ensure the facility
is designed to enable good humidity control.
- Calculate
loads at both highest sensible and highest latent load points.
- Select dehumidification technology that provides
the best solution for the client in regard to capital cost, operating cost,
maintenance cost, and reliability of operation.
ES
|
Vincent A. Sakraida, P.E. Vincent.Sakraida@merrick.com
Sakraida is a senior mechanical engineer with Merrick &
Company in their Aurora, CO office. He is a graduate of Georgia Institute of
Technology with a BME and has 25 years of experience designing mechanical
systems for laboratories, pharmaceutical production, industrial, and other high
technology facilities. He has extensive experience designing central plant
systems (steam, chilled water, hot water), lab utilities (RO, DI, compressed
air, N2), and HVAC systems. He is an expert in cleanroom design and has
presented on the topic at LABS21 and Cleanroom East conferences.
Merrick & Company is an employee-owned, national
consulting firm, with more than 350 employees and offices in Colorado, Georgia,
New Mexico and Canada. Founded in 1955, Merrick provides multidisciplinary architect-engineering
services to public and private clients. Public clients include federal agencies
(USDA, DOE, DOD), public universities, and national laboratories. Merrick’s
diverse practice includes laboratories, mission critical facilities, nuclear
facilities, hot cells/glove boxes, roads/streets, land development, and
geospatial solutions. For more information, visit www.merrick.com.
References 1.
Trane/American Standard Inc., “Dehumidify with
Constant-Volume Systems,” Trane Engineering Newsletter, Volume
29, No. 4.
2.
Wendel, M.J., “Dehumidification Technologies,” HPAC
Engineering, March 2005.
3.
Harriman, III, L.G., “The Dehumidification
Handbook – Second Edition,” 1990.
4.
Siemasko, Jeff; manager of marketing and business
development for Munters Corporation Dehumidification Division.
Did you enjoy this article? Click here to subscribe to the magazine.
|
| |
|
|
|