Relative Humidity: What is it?
Relative
humidity (rh) is a function of both the moisture in the air and the
air temperature. It is equal to the amount of moisture in the air
relative to the amount of moisture the air could hold if it were 100%
saturated (e.g., fog). Air that has an rh of 50% has 50% of the
moisture it can hold at that drybulb temperature. Therefore, rh can
be lowered by either decreasing the moisture in the air, or raising
the air temperature.
Some
terminology:
- Dewpoint: the temperature at which air is saturated with
moisture, i.e., at 100% rh
- Drybulb
temperature: sensible temperature that a thermometer reads
- Wetbulb temperature: temperature of a wet surface that is
evaporating in equilibrium with the surrounding air in an adiabatic
process
In most
applications, increasing space temperature substantially is not an
option. Ninety-degree air at 50% rh is very uncomfortable. People
tend to declare that such conditions are “100% humidity.” Hardly.
One hundred percent rh means the dewpoint equals the air temperature.
A dewpoint of 80°F is very high and very rare. The typical
meteorological year in Miami does not include dewpoints that
high.
We need to control moisture and
temperature. Typical parameters include controlling space
temperatures between 73°F to 75°, and 50% rh. It just so happens
that air with a dewpoint of 55° and a drybulb temperature of 75°
has an rh of almost exactly 50%. Many air-handling systems with
mechanical cooling (chilled water or direct expansion) are controlled
to a discharge temperature of 55° or slightly lower.
Reheat
|
|
| FIGURE 2. DOAS with reheat and downstream cooling. |
|
Dehumidification
via mechanical cooling occurs by driving the conditioned air
temperature down to the desired dewpoint. When too much air at the
desired dewpoint temperature is supplied to a space, the air must be
reheated to maintain desired conditions. If the target is 50% rh, the
space must be about 74° to 75° if the air-handling system is
reducing air moisture to a 55° dewpoint. Air at 70° with a 55°
dewpoint is out of range at 59% rh, “clammy,” and not acceptable.
This is also close to 60% rh, which presents potential for mold
growth. Heat from building envelope gains, internal gains, and/or
energy sources like natural gas or electric resistance is
needed.
Minimizing reheat energy is often the
difference between an efficient system and an energy hog.
Controls
As
with any energy intensive system or process, controls are critical to
efficient operation. This section provides control strategies to
minimize energy consumption associated with dehumidification.
Dehumidification control strategy #1: Only
cool to the desired dewpoint when necessary. On occasion when space
rh must be controlled for comfort, manufacturing, or material
preservation such as in libraries and museums, air handler discharge
temperature is set to maintain a constant temperature that equals the
dewpoint temperature associated with the desired rh. This can waste
energy from unnecessary mechanical cooling, reheat, or both.
Air handler discharge should be reset as high
as possible to maintain temperature in the warmest zone served, with
an override for humidity control. Return air rh is typically
monitored, or in the case of 100% outside air units, indoor sensors
are monitored. Once the rh setpoint is exceeded, the system goes into
dehumidification.
Dehumidification control
strategy #2: Control cooling using variable volume to the maximum
extent possible. Most energy codes (International Energy Conservation
Code 2006) require that VAV systems be capable of reducing airflow to
0.4 cfm/sq ft, or 30% of design flow, or ASHRAE Standard 62
ventilation levels, whichever is greater. In many existing buildings,
the minimum zone flow, or minimum VAV box position, is higher than
some or all of these metrics.
Sensible
cooling delivered to a space is proportional to the product of
difference in space temperature and supply temperature, and
airflow.
Q α (TSpace
– TSupply)
x cfm
When
cooling delivered by the supply air is greater than the load, the
supply temperature must rise, or the airflow must be decreased. If
flow is not low enough while maintaining a desired dewpoint
temperature, reheat is required. Therefore, the minimum flow should
be set by ASHRAE Standard 62, which covers both minimum ventilation
levels for occupied spaces and exhaust for restrooms.
One
way to accomplish this is to incorporate occupancy sensor control in
series with CO
2
demand-controlled ventilation. When a space is unoccupied, the
minimum box position is set to 0 cfm. During normal business hours,
the VAV box controls only temperature when these spaces are
unoccupied. As the space becomes occupied, the box will open to the
minimum required for the area component of ASHRAE Standard 62. As CO
2
rises, indicating a greater rate of occupant pollutant production,
the minimum box position increases.
In many
cases, total system airflow can be reduced to almost as low as the
required exhaust flow, essentially turning air-handling systems into
100% outside air units. Minimizing flow minimizes dehumidification
energy both for cooling and any reheat, as well as fan energy.
Systems that are constant volume — such as
dual-duct, multi-zone, or constant volume reheat — are likely to be
near the end of their expected life and should be converted to VAV.
Many times, this can be done by installing VAV boxes and new digital
controls, with little ductwork modifications and relatively minor air
handler upgrades.
In many cases, spaces that
require significant exhaust including laboratories, kitchens, and
locker rooms have their own dedicated makeup air units. These units
are typically single-zone but they should also have variable volume
capability. Single-zone systems are good candidates for VAV and they
convert easily with a VFD. Temperature is controlled first by heating
or cooling valve position, and then fan speed. This again minimizes
cooling, reheat, and fan energy. Control sequences may need to be
modified to provide better space air mixing if stratification becomes
a problem, especially during the heating season, or if “dumping”
occurs in cooling mode.
Dehumidification
control strategy #3: Keep the building positively pressurized. When
exhaust flow is greater than makeup air supplied, buildings are
negatively pressurized and numerous problems can occur, including
temperature and humidity control problems, as untreated air is drawn
into the building. If a building is negatively pressurized overnight
when most air handling systems are in unoccupied mode, there is a
risk of freezing coils in air handlers or pipes in plenum spaces in
northern climates.
Dehumidification control
strategy #4: Shut down outside air when the building is unoccupied.
This may sound like a no-brainer, but sometimes air conditioning is
used in attempt to dry out a building when a space is unoccupied.
School or university buildings that have floors waxed or carpet
shampooed are good examples. The systems are placed in occupied mode
to drive the temperature down to try to dry the spaces. The problem
with this is that the source of moisture from outdoors is not shut
down. Typically these buildings are not running boilers for reheat,
and there are no internal heat gains from lighting, equipment, or
people to provide a sensible cooling load. As a result, air
conditioning coils are either running at relatively high temperature
in the case of systems with chilled water, or direct expansion coils
are cycling on and off, or using hot gas bypass to artificially load
the unit. In either case, moisture is not being extracted to drive
down the dewpoint, and in the case of hot gas bypass, the unit is
wasting compressor energy.
With relatively
high dewpoint temperatures that approach space drybulb temperature,
humidity rises and the building gets clammy as described above. The
dewpoint of the air in the building tracks the outside air dewpoint.
In some cases, space temperatures are set lower to dry the air. This
actually increases rh in many cases.
One
strategy for drying out a building with minimal internal gains is to
let nature provide reheat via skin heat gains. Again, higher
temperatures tend to decrease rh, but in this case they also increase
evaporation from the building materials. Increased evaporation, of
course, tends to increase rh. Condition the air to the desired
dewpoint periodically during the day, and let the building reheat on
its own. Of course, this works best during hot weather that provides
the most “reheat.”
Systems
|
|
| FIGURE 3. DOAS with energy recovery. (Figure courtesy of Laboratories for the 21st Century, U.S. EPA.) |
|
Another
strategy for minimizing dehumidification energy is to select
equipment and design air handling systems to provide built-in energy
efficiency.
Dehumidification system design
strategy #1: Dedicated outdoor air systems (DOAS). DOAS treat outdoor
air independently from zone temperature control. The makeup air unit
in the DOAS provides pre-treated ventilation to the temperature
control zones. In the cooling season, dehumidification takes place in
the DOAS. Zone temperature control is provided by fancoil units, heat
pumps, or chilled beams and some type of zone heat such as fintube
convection systems or radiant heat. The advantage to this design,
when controlled effectively, is that it can minimize or eliminate the
need for reheat.
However, the key word in the
previous sentence is “can.” Oftentimes, the makeup air unit
serving the DOAS is controlled to provide temperature-neutral air
(70°) all year. This is a mistake and wastes energy most of the time
in typical DOAS. Heating air to above 55° in the winter or reheating
to above 55° after dehumidifying outdoor air in the summer often
results in unnecessary simultaneous heating and cooling. For example,
ventilation air may be driven down to maintain space rh, and the air
is then reheated to a neutral 70°. This air then makes its way to
mix with return air and in many cases must be cooled at the zone to
maintain space temperature setpoints. Even if the reheat is free from
some sort of heat recovery, unnecessary cooling energy is consumed at
the zone. Figure 2 demonstrates wasted reheat and re-cooling
associated with a DOAS makeup air unit with downstream cooling
(Figure 2).
Dehumidification control strategy
#5: Provide minimal temperature control with DOAS makeup air units.
In the heating season, outdoor air should be heated to no more than
55°. In some cases, maintaining an even lower temperature saves
energy by providing more free cooling to zones that need it, although
drafts and condensation on ductwork in the building must be avoided.
When dehumidification is required, drive the outdoor air temperature
down to maintain desired rh and leave it there. Typically, when
dehumidification is required, more zones being served by the DOAS
require cooling rather than heating.
If heat
recovery from the condenser of the makeup air unit or some other free
heat source is available, and the BAS maintains status of heating and
cooling in each zone, the discharge air temperature on the makeup air
unit may be reset to minimize energy consumption. However, this is a
complicated algorithm and it really only applies during light cooling
loads. During periods of greater cooling loads, 55° air from the
makeup air unit is not wasted because it is typically mixed with 70%
to 90% return air, providing little cooling for the space. In other
words, there is no overcooling and reheat.
Dehumidification
system design strategy #2: Precool and reheat ventilation air with
energy recovery. In some facilities such as laboratories, the need
for makeup air is so great that reheat cannot be avoided. In these
systems, an energy recovery unit with pre-cooling and reheating
provided by energy recovery is a low energy-cost option. In
dehumidification, outdoor air is precooled by exhaust air. The fresh
air is then cooled to the desired dewpoint with mechanical cooling
and then reheated again by the exhaust air. The exhaust air that
gives up heat to the fresh air discharge is cooled in preparation to
extract heat from the incoming ventilation air. Dry tempered air is
delivered to the zones that are again conditioned using fancoil
units, heat pumps, or chilled beams with some other source of heating
(Figure 3).
Figure 3 provides a line diagram
of an energy recovery unit that can be used for dehumidification. Air
enters at 93°, 51% rh, and a dewpoint of 72°. It is dehumidified to
a dewpoint of 54°, with a 65% reduction in cooling energy and 100%
reduction in reheat. Note, however, that even at 67°, large amounts
of this cool dry air provide substantial space cooling, and therefore
some reheat may be inevitable.