Next-Generation Cooling Is Looking Up
by Carl C. Schultz, P.E.
May 2, 2007
No
one likes being wrong, and I suppose that consulting engineers like myself may
hold this sentiment more strongly than others. However, I will take this risk
by making a prediction that VAV systems will lose their place as the system of
choice for large commercial applications at some point during the course of my
career.
It should be realized that the
VAV system, which has served us well by providing comfort and working to ensure
the health of building occupants, is unfortunately an energy abuser. This may
seem an unfair characterization, since VAV rescued us from the constant volume
reheat era that existed prior to the energy crisis of the 1970s. However, this
system relies on electric-powered fans pushing large volumes of air through a
distribution network consisting of bent sheet metal, screws, and lots of
adhesive. If the comfort of the building occupant is threatened, a control system
will reduce the amount of air delivered and, as a last resort, the air will
then be reheated.
HVAC systems consume enough of
the world’s energy that others outside of our industry are beginning to take an
interest in what we do for a living and are watching and commenting on how we
conduct our business. You may have noticed that the political and social
climate is changing and that this could significantly influence the way we
design building services very soon. So what does all of this have to do with chilled
beams? Well, this technology is one of several that promises to offer relief
from the excessive use of fan energy as well as from the reliance on reheat to
achieve comfort.
Individuals
in our midst are on a quest to uncover an HVAC system that will reduce energy
consumption while not compromising the level of comfort to which our clients
have grown accustomed. Not only can chilled beams decrease energy use, but they
can also increase building efficiency by reducing the floor space required for
mechanical rooms and by decreasing the floor-to-floor height required for
ductwork.
Many technologies have the
potential to positively alter the built environment, while others merely
possess a unique approach and have been subsequently exploited by marketing departments.
Chilled
beam technology should not be confused with radiant cooling, although there are
some similarities. Chilled beams are mounted overhead, whereas radiant cooling
can be in the form of piping in the floor slab, capillary mats integrated into
walls and ceilings, as well as tubing mounted to the back of ceiling panels.
Radiant cooling systems do not employ fans, while certain chilled beam
approaches do. Both radiant cooling and chilled beams utilize warmer chilled
water temperatures and require a dry atmosphere to prevent condensation.
However, an important difference
is that chilled beams rely mainly on convection, as opposed to radiation, to
transport heat from the space they serve. Chilled beams have been manufactured
and used in Europe and Australia for about 15 years, but they are now getting
noticed in the U.S. due to the efforts of individuals and organizations
interested in tackling the perceived problem of building energy use.
 |
| Position chilled beams to maximize performance
and enhance comfort, such as using perforated ceilings with at least 50% free
area below the beam to reduce the risk of uncomfortable drafts. (Photo courtesy
of Halton.) |
|
|
Chilled Beams
The term “chilled beam” should
not be construed to imply that the building structural elements are utilized or
incorporated into the construction of these devices, as they are simply
standalone components that are typically hung at the ceiling level from the
building structure. Certain radiant cooling systems are, however, integrated
into the building either in the slab or plastered into the walls or ceiling. A
chilled beam is constructed of copper tubing mechanically bonded to aluminum
fins, all housed into a sheet metal enclosure for aesthetics.
There
are two categories of chilled beams. The first is the static or passive beam
that relies on natural convection to accelerate warm air at the top of the room
past the cool finned elements of the beam. The passive chilled beam can also be
manufactured in a “hybrid” manner to incorporate a radiant ceiling panel
feature to augment the convective heat transfer.
The
second type of device is termed a ventilated or active beam and uses
conditioned outdoor air ducted from a central system to pass over the cooling
element. The active beam can also be designed so that the ducted ventilation
air is delivered at a high velocity to aid the convection process by inducing
three to five times the amount of room air past the cooling element. Active
beams can be of either the open or closed type with the latter designed so that
only room air is induced over the heat exchanger, keeping the air located above
the ceiling plenum out of the process. These active beams are similar to the
high-pressure induction units that can still be found in many U.S. high-rise
buildings constructed years ago.
A chilled beam can be specified
with many useful features in what is termed an integrated service beam. Service
beams can include direct and indirect lighting, occupancy and daylight sensors,
smoke detectors, public announcement speakers, openings for sprinklers, as well
as cabling and pathways for voice, data, and power.
These
beams can be specified with isolation and control valves as well as the
attendant piping specialties, which would be housed in an extension of the beam
and reached through integral access doors. Service beams can be mounted
exposed, can be incorporated into a suspended ceiling, and in fact, can be
designed to include the ceiling system as one complete assembly. The advantages
to this approach are a single source of responsibility for many building
service components as well as minimizing coordination and perhaps overall
installed cost.
Application
There
is an art to the positioning of chilled beams to maximize performance and to
enhance occupant comfort. For instance, passive chilled beams can be placed
parallel to exterior perimeter walls to counteract the effects of solar gain.
In fact, the rising warm air near windows that will naturally come in contact
with the cooling element will increase its effectiveness as a heat exchanger.
There should be sufficient space between the top of the chilled beam and the
underside of the structure to ensure that the naturally buoyant warm air can
rise up past the beam, make its turn, and then accelerate past the cool fins of
the heat exchanger. The velocity is highest directly below the passive beam and
therefore, these beams should not be placed directly above workstations. The
use of perforated ceilings with at least a 50% free area can reduce the risk of
potentially uncomfortable drafts below the beam.
Likewise, placing a passive beam
directly above a high heat load such as a copy machine can reduce the capacity
of the beam, as the rising warm air will counteract the falling current of cool
air attempting to develop off the beam.
Unlike passive beams, active
beams can be placed directly over workstations and high convective loads, as
these types of beams induce warmer room air up through their center and then
disperse the air laterally across the top of the room. This is similar to the
Coanda effect generated by high induction diffusers in the cooling mode. However,
the upward convective flow of internal heat loads located further away can
affect the performance of an active beam by disturbing the cool jet of air
leaving the beam.
The recommendations appear to be
mixed on the positioning of active beams, as it is most economical to maintain
long runs, which usually means positioning them perpendicular to the exterior
walls, even in shallow buildings. This approach is reserved for large open
office areas and in the case of enclosed offices at the perimeter, the beams
are often positioned parallel to the outside wall. However, in cold climates
this can work to cause drafts along the windows unless a unidirectional beam is
selected.
The literature on active and
passive beams seems to point to an inherent sensitivity in these devices that
may warrant attention by the designer in applying these products. There is
mention of constructing full-scale mock-ups as well as the use of computational
fluid dynamics, which are not normal design procedures in the U.S. However,
manufacturers can provide software and assistance in the application of their
chilled beam products.
Beams have been used outside of
the U.S. for about 15 years, so there is sufficient information available, but
it is predominantly in metric units. The cooling capacity of an active chilled
beam is roughly 80 Btuh/sq ft (250 W/m2) and can be
stretched to 110 Btuh/sq ft (350 W/m2). Passive beams
have a lower output at about 50 Btuh/sq ft (150 W/m2)
and peaking at the lower end of the active beam range of 80 Btuh/sq ft (250
W/m2).
This
being said, there are recommended cooling design values for the application of
chilled beams, which are lower that the catalogued output. The recommended
“optimum” range is between 20 Btuh/sq ft (60 W/m2) and 25 Btuh/sq ft (80 W/m2) or roughly 500 to 600 sq ft/ton. This capacity
is more than adequate for many commercial applications considering that the
ventilation load would be handled by another system.
The
limits of active and passive beams can be increased to accommodate even severe
cooling conditions imposed by a high solar gain and thermal conductance through
the building façade. Even so, it should be stressed that all new construction,
whether using chilled beams or conventional technologies, should proceed with
the commitment for a tight building and a high-performance envelope that would
include pressure testing, enhanced insulation, and spectrally selective
glazing.
Because
chilled beams are mainly a convective technology and are mounted at the ceiling
level, their effectiveness in the heating mode is limited and should not be
expected to produce more than about 8 Btuh/sq ft (25 W/m2) to 16 Btuh/sq ft (50 W/m2). This upper end should be considered adequate
for many applications even in cold climates, as the often-significant
ventilation load is taken care of elsewhere.
Nonetheless,
it is prudent to consider using a perimeter heating system, especially beneath
windows. The concept of heating with active beams as opposed to passive beams
makes more sense as the active beams have the ducted ventilation air as a
motive force. For this reason, the ventilation system needs to be operating for
the beam system to meaningfully contribute to the heating of the building.
Passive beams rely indirectly on currents developed from cold glass and
ventilation air from nearby diffusers, but you do not want placement of
diffusers to interfere with passive chilled beam operation in the cooling mode.
Distribution And Control Systems
A
critical element in the successful application of chilled beam systems is
condensation control where one must ensure that the beam and associated piping
specialties do not drop below the ambient dewpoint for sustained periods.
Elevating the entering water temperature can work to a point, unless there are
high sensible loads that would make maintaining the drybulb setpoint
impossible. Typical entering chilled water temperatures range between 57°F and
64° (14°to 18°C) and the more daring practitioner may aim for a room dewpoint
temperature equal to this value and therefore may specify insulation on the
valves and piping to the chilled beam.
A more conservative approach is
to keep the room dewpoint temperature a couple of degrees below the entering
supply water temperature, which means that after accounting for latent loads in
the space, that the introduction of ventilation air would result in dewpoint
temperatures between roughly 56° and 62° (13° to 17°C ).
With regard to piping and
insulation, a vapor barrier need not be included on the piping systems in many
applications and some designers choose to use an uninsulated, thick-wall
plastic piping system, as the thermal resistance of the plastic keeps the
surface temperature warmer than metallic pipe.
The chilled beam concept does not
preclude the use of natural ventilation or operable windows, as there are
installations that use devices such as dewpoint sensors and window position
switches to automatically raise chilled water temperatures or to shut off flow
to beams when the situation warrants.
Interesting central plant
concepts can develop from the use of chilled beams, with one being that during
warm weather chilled water generated at a traditional 44° (7°C) can first be
run through a dedicated outside air unit and the return water from this unit
can then be delivered to the chilled beams. The temperature drop across the
beam can be expected to be about 7° (4°C), which would yield return water
temperatures in the mid 60°s to perhaps 70° (21°C). This could result in an
efficient multistage central chilled water plant.
Low
outdoor air dewpoint temperatures during cool weather allow the ventilation
system to operate without the need for chilled water and the chilled water
central plant can then distribute directly to the chilled beam system and with
the warmer temperature requirements.
A better approach would be to
allow chilled water to pass through the ventilation system cooling coils where
it can do double duty by pre-heating the outdoor air as well as obtain some
free cooling for the chilled beam loop. With warmer loop temperatures there can
be extended periods where free cooling can be obtained from a cooling
tower-driven waterside economizer or through a ground coupled heat exchanger.
In fact, well water or deep surface water may be able to provide a year-round
source of cooling by supplying roughly 60° water without the need for a refrigeration
system.
As
chilled beams operate to cool the building, the building ventilation system
need only be sized to account for the amount of fresh air needed, which can
drastically reduce the size of the system in many applications. The fresh air
can also be controlled and directed in a more accurate manner by having it
delivered based upon space requirements. Ventilation systems can be constant or
variable volume, high or low pressure, and air can be delivered overhead
through diffusers or active beams.
Air can also be delivered low, in
a displacement ventilation configuration or can be supplied in an underfloor
application. A benefit to the designer is that there would be no need for the
laborious “XYZ equation” that plan examiners have become fond of scrutinizing.
With lower airflow rates, reheat
energy can be eliminated along with the capital expenditures associated with
this wasteful practice. The ventilation system equipment can be configured with
heat recovery to extract energy from the air before being relieved from the
building and with no return airstream to contend with, a portion of the heat
generated by the lighting system leaves the building before it has a chance to
reach a cooling coil and contribute to the load.
A
system that relies mainly on passive, as opposed to active, beams may have
large areas that may be able to be designed without the use of room thermostats
as these beams can be somewhat self-regulating when the design chilled water
temperatures happen to be close to the room temperature. As load begins to be
imposed upon the room, the room temperature will rise, thereby increasing the
temperature difference between the space and the beam, which will consequently
increase its output.
It seems natural that when
designing the cooling system around chilled beams, choosing a radiant heating
method may compliment the cooling system. Radiant heating applications often
require lower water temperatures than other types of heating systems, which can
lead to a more energy-efficient heating plant if condensing boilers are used
since the return water temperature is cooler and can therefore extract more
heat from the flue gases.
Conclusions
Social
awareness and the resulting political pressure to reduce energy consumption are
such that even the most stubborn of engineers must sense this changing
environment. Consequently, it is our responsibility to explore concepts that
have the potential to accommodate society’s desire for positive change in the way
we design, build, and operate buildings. The aspect that makes chilled beams
such a promising technology is its emancipation from reheat as well as from
large fan systems and the resulting reliance upon obtrusive ductwork.
Besides the benefit of conserving energy, I
believe that it would be nice to live in a world where mechanical engineers do
not have to wrestle with architects over issues such as floor-to-floor heights
and the size of rooms for central ventilation systems. None of this information
presented here is new; however, I have become a convert of what I envision as
perhaps the next big HVAC trend, which is to minimize both fan and reheat
energy. What VAV systems were to the last three decades, chilled beams or
similar concepts could be to the next three. ES
|