Energy In Data Centers: Benchmarking and Lessons Learned
by Dr. MUNTHER SALIM PH.D.
April 1, 2009
If
you work in data centers, then the PUE matters to you. Look into some
ways to reduce the cooling system’s power consumption, understand
the impact of climate zone and size, and perhaps improve your
facility’s benchmark along the way.
Recently,
various organizations have pursued efforts to develop further
understanding and benchmarking of data center energy efficiency.
Numerous potential regulatory and institutional initiatives have
driven these efforts. The U.S. Environmental Protection Agency (EPA)
“Report to Congress on Server and Data Center Energy Efficiency”
(2007/8) and the European Commission’s “Code of Conduct on Data
Centres Energy Efficiency, Version 1” (2008) are only two examples
of regulatory interest in data center efficiency.
|
|
| TABLE 1. An example of potential data center benchmarks. |
|
Future
rules and regulations regarding data center power consumption will
clearly be led by the federal government. The DOE and the EPA are
currently pursuing and establishing benchmarks and guidelines that
they could in turn enforce at some point in the future. In 2007, the
DOE Office of Energy Efficiency and Renewable Energy launched its
“Save-Energy-Now” campaign which is considered DOE’s first
attempt to seriously address data center efficiency while the EPA is
actively developing an Energy Star rating for data centers.
THE METRICS SYSTEM
|
|
| TABLE 2. Average power usage effectiveness (PUE) of various data center sizes. |
|
Perhaps
the only practical metrics that exist are those developed by The
Green Grid, an industry consortium active in developing metrics and
standards for the IT industry. This article presents a summary of
energy audit and optimization studies conducted on 25 data
centers, including comparison of their power usage effectiveness
(PUE) and data center infrastructure efficiency (DCiE). As shown in
Figure 1, PUE is defined as data center total power divided by IT
equipment power. PUE is always higher than unity, and the closer it
is to unity the better the performance; its reciprocal, the DCiE, is
a fraction or percentage. The higher the DCiE, the more efficient the
data center is considered. Similarly, a
mechanical PUE and electrical PUE can be defined. PUEmechanical
is obtained by dividing the energy consumed by the mechanical
infrastructure by the IT equipment power; this indicates the
effectiveness of the HVAC system. PUEelectrical
is defined as the total electrical power (electrical losses
plus lighting power plus IT power) divided by the IT power.
PUEelectrical
results in a number that is larger than one. The lower this
number, the more efficient the electrical infrastructure. Figure 2
depicts a summary of the annual average PUE obtained in various
climate zones. (A combination of power measurements and data trends
from a BMS was used to calculate these metrics.)
|
|
| FIGURE 1. Data center components and PUE. |
|
Figure
2 shows PUEs ranging from around 1.7 to 3.6, with an average of 2.34.
On average, data centers consume an additional 1.34 kW for every kW
going to an IT application. If one were to
benchmark the 25 data centers in terms of a PUE according to the
hypothetical criteria shown in Table 1, this would result in the
following:
- “D”
rating: 32%
- “E” rating: 36%
- “F” rating or poor: 32%
|
|
| Table 3. Case study one. 1.Cumulative cost is the total costof all recommendations or energy-efficiency measures that arerequired to reach to the next rating level. For the example above,the rough order of magnitude (ROM) cost is $300k to $400k toincrease the DCiE from 0.52 (D) to 0.60 (C). Similarly, to increasethe rating from D to B, the cumulative ROM cost is $600K to $1M.2.Simple payback is calculated as the cumulative cost divided bythe projected annual energy savings. |
|
Therefore,
unfortunately, we can expect one in three data centers to fail to
achieve benchmarking recognition (F rating or poor). In fact, the
highest DCiE achieved by any of the data centers in this database is
0.60 (D rating, PUE=1.67). None of the data centers audited to date
achieved a “C” rating or higher. Interestingly,
the database indicated that small data centers (raised floor area
[RFA] < 10,000 sq ft) illustrates this point. Small data centers
were observed to have partially populated IT equipment racks and
floors, oversized and aging cooling systems, higher levels of air
mixing (recirculation and bypass air) in the raised floor areas, no
implementation of free cooling, low UPS load factors, and no direct
cooperation between the IT and the facilities departments.
Enterprise
data centers were more likely to implement energy saving techniques
such as free cooling as well as benefit from higher levels of
cooperation between IT and facilities. The staff in these larger data
centers were also more likely to stay informed about new advances in
their fields and industry best practices by participating in
professional seminars Generally speaking,
energy efficiency measures required to upgrade a benchmark rating
from “F” to “E” can be implemented with little or no
investment; these measures have a quick payback. In many scenarios,
those measures may even lift the rating to the next level, “D.”
The typical low-hanging fruit that can be found by data center
operators may include measures such as shutting down extra cooling
units (beyond design redundancy) due to overcooling, widening
humidification tolerances, raising air temperature setpoints in
cooling units, disabling reheat elements, installing blanking panels,
and sealing floor cut-outs with cable brushes to improve air
management. However, substantial investments are necessary to achieve
high benchmark ratings.
CASE STUDY ONE
|
|
| FIGURE 2. Average annual PUE of data centers in various climate zones. |
|
Case
study one (Table 3) is a 1 MW IT load (30,000 sq ft of raised floor)
data center in climate zone (5A) rated currently at DCiE=0.52,
PUE=1.94 “D.” Table 3 is represented in
Figure 3. It shows that the cost to upgrade will increase but not
necessarily linearly. Upgrading to ratings “B” and “A” will
require substantial investment.
CASE STUDY TWO
|
|
| FIGURE 3. PUE improvement for case study one. |
|
Case
study two (Table 4) is a 200-kW IT load (22,000 sq ft of
raised floor partially populated) data center in climate (4A) rated
currently at DCiE=0.35 (PUE=2.86 or F “poor”)
CLIMATE IMPACT
|
|
| FIGURE 4. PUE improvement for case study two. |
|
The
effect of climate zone on energy efficiency is also important. Figure
5 is derived from actual data, and the impact of climate zone is
clearly evidenced. Zone 1 is the hottest, and 7 is the coldest,
(Zones 6 and 7 are not shown as there were no data from data centers
in those two zones). In addition, the zone designation includes an
alphabetic designation: Here A stands for moist, B stands for dry or
desert, and C stands for marine conditions. For example, Chicago is
Zone 5A while Miami is 1A. Colder climate zones offer potential for
“free cooling directly via an air economizer or indirectly via a
waterside economizer, which can provide substantial reductions in
mechanical power consumption and improved PUE. Operators
of a data center in Phoenix (Zone 2B) may have limited options for
lowering PUE than operators of a data center in San Francisco (3C).
The high year-round ambient temperature in Phoenix makes it more
difficult to make use of energy-reduction strategies such as
economizers and VFDs.
|
|
| FIGURE 5. Climate zone impact on data center energy efficiency. |
|
In
contrast, mechanical data center cooling systems in colder climates
will consume less power because the components are more efficient at
cooler temperatures. The cooler climate supports more
energy-efficiency measures than hot climates. For example, in San
Francisco, air economizers have been implemented successfully to cool
IT equipment with outdoor air for more than 7,000 hrs/yr. In the
Chicago area (5A), waterside economizers can be used to eliminate
power consumption by chillers for at least 25% of the year, resulting
in an overall reduction of the data center total power or PUE by 10%
to 15%.
LOW PUE DATA CENTER
|
|
| TABLE 5. Summary of data center energy audits. |
|
n
general, low PUE data centers will have efficient cooling systems and
use airside economizers outside air for cooling or waterside
economizers with VFDs on every possible component. Additionally,
those data centers will have high chilled water setpoints, high
servers intake air temperatures, and wide humidification ranges.
Finally, those data centers will have completely enclosed cold or hot
aisles or physically isolate the two to separate cool air from warm
air. On the electrical side, these facilities will have an
uninterruptible power supply (UPS), load factors of 40% and
associated UPS efficiencies higher than 96%, and perhaps occupancy
sensor-controlled lighting systems.
|
|
| FIGURE 6. Data center average power consumption. |
|
Recently,
containerized solutions or data centers in a box have been gaining
ground. These solutions are expected to yield lower PUEs than
conventional design. A preliminary simulation yielded a PUE of 1.25
for a container data box compared to 1.52 for a state-of-the-art data
center in Zone 5A; this translates to savings of hundreds of
thousands of dollars annually. Generally
speaking, the power allocation in a typical data center (PUE~2) is
shown in Figure 6. Aside from the IT equipment
power, Figure 6 reflects the fact that most energy-efficiency
measures can be implemented in the mechanical cooling system whereas
limited options are available for the electrical infrastructure.
Mechanically, the cooling system and the data center fans represent
the major energy consuming components, while the UPS and the lighting
systems are usually the only areas where gains can be made
practically in the electrical system. The cooling load can be reduced
by implementing economizers and VFDs on the chillers, and by raising
the chilled water setpoints and implementing condenser water reset
control as weather permits. Similarly, implementing variable airflow
can reduce the fan power consumption by up to 40%.
GENERAL CONCLUSIONS
The
analyses in Table 5 were based on a fixed cost per kWh. Cost of power
varies between the different geographical areas. In Boston, which is
located in Zone (6A) for example, the cost of electricity is
$0.16/kWh, whereas the cost in Phoenix (Zone 2B) is $0.08/kWh.
Additionally, some parts of the U.S. have more green power than
others. The green power plants (wind, solar, etc.) result in less
associated carbon footprint. The data centers in the database were
grouped into three different categories based on their size. For
small data centers, reduction of the PUE from 3 to 2.3 would require
small investment of about $165K, which would be paid back in about 3
years and that would result in 300 metric tons of carbon dioxide
avoidance. Further analyses are shown in Table 5 for other
categories. ES
REFERENCES
United
States Department of Energy (DOE). U.S Government Computer News.
http://www.gcn.com/online/vol1_no1/46419-1.html,
2008. United States Environmental Protection
Agency. Report to Congress on Server and Data Center Energy
Efficiency Public Law 109-431, ENERGY STAR Program,
2007. U.S. DOE. Save Energy Now Initiative.
http://www1.eere.energy.gov/industry/saveenergynow/partnering_data_centers.htm,
2007. European
Union Code of Conduct for Data Centres.
http://re.jrc.ec.europa.eu/energyefficiency/html/standby_initiative_data%20centres.htm,
2008. The Green
Grid. “The Green Grid Data Center Power Efficiency Metrics: PUE and
DCiE.” http://www.thegreengrid.org/gg_content/TGG_Data_Center_Power_Efficiency_Metrics_PUE_and_DCiE.pdf,
December 2007.
|