by DonFisher, P.E. Vernon A. Smith, P.E. May 1, 2007
The
energy intensity and utility costs associated with operating a commercial
kitchen ventilation (CKV) system are well recognized within the HVAC design
community. However, there is no piece of equipment that generates more
controversy within the foodservice industry than the exhaust hood, in all its
styles and makeup air combinations. From the onset of a commercial kitchen
project, the design of the exhaust ventilation system is challenged by an
inherent disconnect between the foodservice consultant and the mechanical
engineer.1
The
capacities of exhaust hoods in commercial kitchens range considerably from 500
to 1,500 cfm in coffee shops and delis; from 1,000 to 5,000 cfm in quick service restaurants; from 4,000 to 12,000
cfm in casual and full-service operations; and from 10,000 to 30,000 cfm in
large institutional kitchens.
All in all, there are three
billion cfm being exhausted from commercial kitchens in the U.S. The
conditioning of the outdoor air that is required to replace the air exhausted
from the kitchen, along with the associated fan energy, imposes a significant
energy burden — at least 50% of the total HVAC load in commercial foodservice
facilities.
Designing For Precise Flow
There is often an underlying
supposition that the exhaust hood will function satisfactorily if it is
specified in accordance with its UL-listed airflow capacity. This may be far
from reality! Research over the past 10 years has demonstrated that hood type
and local introduction of makeup air have a significant impact on exhaust and
makeup air ventilation rates. Integrating the CKV system with the
front-of-the-house HVAC system has the potential to lower the energy burden and
improve kitchen comfort by maximizing the transfer of outdoor air supplied to
the dining room as a contribution to the makeup air requirement. A related and
appealing energy saving strategy is the application of demand ventilation
control to kitchen exhaust systems.
The replacement air required for
commercial kitchen ventilation systems is always 100% of the exhaust air — what
goes out must come in. A common design practice is to supply at least 80% of
replacement air using an independent makeup air unit (MAU) with the remaining
20% supplied by conditioned outside air from HVAC units serving the kitchen or
transfer air from adjacent spaces. This keeps the kitchen under a negative
pressure (relative to the dining room) to prevent cooking odors from migrating
into the dining area.
In
many climates, the replacement air from an independent MAU is not conditioned,
which may create uncomfortable conditions (too cold and/or too hot) in the
kitchen. In other climates, the makeup air is heated, which in many cases
results in simultaneous heating (by the MAU) and cooling (by the HVAC unit) of
the kitchen during the shoulder seasons.
Conventional design practice does
not take full advantage of the relatively high rate of occupancy ventilation
air that is introduced into the dining room or other areas of the building
adjacent to the kitchen. There is an opportunity to use this code-required
(based on ASHRAE Standard 62) outdoor air supplied to the dining room as
replacement air for the exhaust hood, thus reducing (or in some cases, even
eliminating) the fraction of replacement air from the independent MAU. Since
occupancy ventilation air is conditioned in most cases, transferring it to the
kitchen as a contribution to the replacement air requirement can improve
comfort conditions in the kitchen.
The following approach is
recommended2 for optimizing the design of a CKV system.
Minimize the design exhaust ventilation rate.This involves appropriate selection
of the type and style of exhaust hood for the line of cooking equipment.
Accomplish this with prudent selection and application of UL-listed hoods and
by considering the “exhaust flow” recommendations from hood suppliers for the
cook line. Exhaust hood manufacturers’ engineering departments have a lot of
knowledge that consulting engineers can tap to select an appropriate exhaust
rate and enhance the specifications with details such as increasing overhang,
minimizing the rear gap (between appliances and back wall), adding side panels,
and using proximity-style hoods where appropriate. Incorporating demand
ventilation controls falls within the scope of minimizing the exhaust ventilation
rate and associated energy burden.
Integrate the CKV system with the building HVAC
system. This design step is one
that is easily skipped, since the specification of a dedicated makeup air
system to replace 80% of the exhaust air ensures air balance and facilitates
plan check. However, it does not facilitate system optimization (from either an
energy efficiency or a kitchen comfort perspective). The goal is to utilize as
much Standard 62 outdoor air from the dining room and other spaces as possible
as a contribution to the replacement air requirement. Maximizing transfer air
is the key to HVAC system integration. Not only can hood performance be
superior, the kitchen environment will benefit from the cooling contribution of
the “recycled” dining room air.
Minimize dedicated makeup air volume and velocity.
This concept is counter to general practice,
as locally supplied makeup air is often the easiest design solution. However,
locally supplied makeup introduces air quantities and velocities that often
interfere with the ability of the exhaust hood to capture and contain cooking
effluent. Once the transfer airflow rate has been established, the quantity of
dedicated makeup air is determined by subtracting the amount of transfer air
from the total exhaust air volume. Introduce this reduced amount of makeup air
at the lowest velocity possible by maximizing the area of the supply grilles.
Do not specify four-way diffusers anywhere near exhaust hoods. Perforated plate
diffusers are preferred.
Let’s
take a closer look at how hood specifications and makeup air introduction can
affect the design exhaust rate and system performance.
The hood factor
– capture and containment (C&C). The
design exhaust rate depends on the hood style and construction features, as
well as factors mentioned above. Wall-mounted canopy hoods, island (single or
double) canopy hoods, and proximity (backshelf, pass-over, or eyebrow) hoods
all have different capture areas and are mounted at different heights and
horizontal positions relative to the cooking equipment.
Generally,
for a given line of appliances, a single-island ceiling-hung canopy hood will
require significantly more exhaust than a wall-mounted canopy hood, and a
wall-mounted canopy hood requires more exhaust than a well-engineered proximity
(e.g., eyebrow-, backshelf- or pass-over-style) hood. The performance of a
double-island ceiling-hung canopy hood tends to emulate the performance of two
back-to-back wall-canopy hoods, although the lack of a physical barrier between
the two hood sections makes this configuration more susceptible to cross
drafts. Single-island canopy hoods present the “ultimate” capture and
containment challenge in hood applications and are typically the foundation of
the problems in display cooking kitchens.
Chapter 31, titled
“Kitchen Ventilation” in the 2003 ASHRAE Handbook — Applications3
provides a table of typical design rates for “listed” hoods. This table was
developed with input from the major hood manufacturers in an effort to provide the
design engineer with a sense of realistic airflow rates for a given hood
application. The ranges reflected in this table are due to the fact that there
are large variations in the cooking effluent challenge for different
foodservice operations, even for the same “duty” category of appliances. It is
also due to the fact that listed hoods are not created equal — some hoods work
better than others. This is why it is important to select the design
ventilation rate using hood manufacturers’ software tools or hood sizing
formulas, rather than their “listed” values.
Side panels. Side
panels or skirts (both partial or full) permit a reduced exhaust rate in most
cases, as more of the replacement air is drawn across the front of the equipment,
improving capture of the effluent plume generated by the hot equipment. They
also mitigate the negative effect of cross drafts. Side panels are a relatively
inexpensive way of improving hood performance. It is important to know that
partial side panels can provide almost the same benefit as full panels.
Laboratory testing has demonstrated reductions in capture and containment
airflow rates up to 100 cfm/ft of hood by the application of partial side
panels on 10-ft wall-canopy hoods. 4
Although defying its definition as an “island” canopy, end panels
can dramatically improve the performance of a double-island or single-island
canopy hood.
Makeup air factor.
Introducing makeup air into the kitchen without disrupting the ability of
the hood to capture and/or without causing discomfort for the kitchen staff is
a huge challenge. Dumping 8,000 cfm of makeup air, for example, along the front
of a 25-ft cook line does not go as smoothly in practice as it appears on a theoretical
air balance schedule. Another way of looking at this is to never “force” air
toward the hood — make the hood do the work and “pull” the air toward itself.
Not only can high makeup air velocities hamper the ability of the hood to
capture and contain cooking effluent, locally supplied makeup air that is too
cold or too hot can create an uncomfortable working environment.
Makeup
air that is supplied through displacement ventilation (DV) diffusers remote
from the hood, perforated diffusers located in or near the ceiling, or as
transfer air from the dining room, generally works best if air velocities
approaching the hood are less than 75 fpm. Makeup air introduced in close
proximity to an exhaust hood, however, has the potential to interfere with the
hood’s ability to capture and contain due to higher velocities. The chances of
makeup air affecting hood performance increases as the percentage of the
locally supplied makeup air (relative to the total exhaust) is increased. In
fact, the 80% rule of thumb for sizing airflow through an MAU can be a recipe
for trouble, particularly if the exhaust capacity has been oversized.
Demand ventilation controls.
The concept of demand controlled ventilation is
attractive within the design of commercial kitchens. While this technology
currently is led by one manufacturer, it is anticipated that other strategies
of demand control will emerge and that its specification in commercial kitchens
will become mainstream. A primary component of DV control is a VFD on both the
exhaust and makeup air fans. Integrated with a sensing system to modulate the
exhaust flow in response to the heat and smoke being produced by the cooking
equipment, DV can yield substantial energy savings. Furthermore, it allows the
engineer to incorporate a larger cfm safety factor within the exhaust hood
specification without an ongoing energy consumption penalty to the foodservice
operator. This safety factor can be “commissioned out” of the system, but it is
always there if needed (a good choice for an island canopy hood, as replacing
the exhaust fan is not the preferred option when the hood fails to perform).
The economic return on a DV control package generally increases with the size
of the project (larger exhaust systems in hospitals, hotels, and casinos).
Bottom Line
Hold “spec” on the design exhaust
rate — it should not be negotiable within the competitive bid or during
evaluation of alternative ventilation system proposals based on a lower
UL-listed cfm value. Do not use short-circuit hoods with internal makeup air
supply.
Commission
the CKV system – air balancing of all exhaust and makeup air, and performance
testing of CKV systems must be included in all jobs, as these actions are
required by most codes, and it “closes the loop” to ensure that all aspects of
the system are functioning as designed.
The science of commercial kitchen ventilation
continues to evolve at a rapid pace, driven by ASHRAE research projects, an
expanding line of innovative products, and research at the Commercial Kitchen
Ventilation Laboratory in Wood Dale, IL. All of this information, along with
the results of a California Energy Commission-funded makeup air research
project, are leading to updates of the national codes (NFPA 96 and IMC) and
fundamentally changing the way CKV systems are designed and operated. ES
Internal makeup air hoods (short
circuit) were developed as a strategy to reduce the amount of conditioned air
required by an exhaust system to meet code requirements by introducing a
portion of untempered makeup air directly into the exhaust hood reservoir.
However, laboratory testing and
field experience have clearly demonstrated that when short circuit hoods are
operated with significant percentages of internal makeup air, they fail to
capture and contain the cooking effluent. 5
Dilution of the cooking effluent with the internally supplied MAU
may make it difficult to visualize spillage, but a degraded kitchen environment
is confirmation that hood performance has been compromised.
Fortunately, the specification of
short-circuit hoods has decreased over the past few years as there are more
effective strategies for reducing the energy burden of a CKV system while
maintaining an acceptable kitchen environment.
Simply stated, short-circuit
hoods are not recommended under any circumstances! This recommendation is
endorsed by leading hood manufacturers, even though they may still include
short-circuit hoods in their catalog and competitively bid a project based on a
short-circuit hood spec. In other cases, the local representative may promote
the concept in pursuit of a marketing advantage and the consultant’s
specification on a project.
DonFisher, P.E. Fisher is president/CEO of Fisher-Nickel, inc.
(FNi), and manages the Food Service Technology Center (FSTC) in San Ramon, CA.
This center collaborates with the Commercial Kitchen Ventilation Laboratory
(CKVL) in Wood Dale, IL to develop and apply standard test methods for
evaluating the performance of food service equipment. The program is funded by
California utility customers and administered by the Pacific Gas and Electric
Company (PG&E) under the auspices of the California Public Utilities
Commission. He received a B.Sc. in Mechanical Engineering in 1972 and a M.Sc.
in Mechanical Engineering in 1974 from the University of Manitoba.
Vern Smith, P.E., is a senior engineer and associate
principal with Architectural Energy Corporation. He is responsible for project
management and engineering analysis for building science related projects and
serves as corporate legal counsel for Architectural Energy Corporation. He has
worked since 1978 in management, contract administration, engineering,
scheduling, and cost control in construction, manufacturing, and consulting
engineering. Since 1992, his assignments have focused on building science and
foodservice energy research, and he is program director for the PIER Buildings
Research Programs titled “Advanced Automated HVAC Fault Detection and
Diagnostics Commercialization,” sponsored by the California Energy Commission.
He is also technical director for the Utility Focused Market Model for Zero
Energy New Homes Project.
Vernon A. Smith, P.E. vsmith@archenergy.com Vern Smith, P.E., is a senior engineer and associate principal with
Architectural Energy Corporation. He is responsible for project management and
engineering analysis for building science related projects and serves as
corporate legal counsel for Architectural Energy Corporation. He has worked
since 1978 in management, contract administration, engineering, scheduling, and
cost control in construction, manufacturing, and consulting engineering. Since
1992, his assignments have focused on building science and foodservice energy
research, and he is program director for the PIER Buildings Research Programs
titled “Advanced Automated HVAC Fault Detection and Diagnostics
Commercialization,” sponsored by the California Energy Commission. He is also
technical director for the Utility Focused Market Model for Zero Energy New
Homes Project.
References Works Cited. <br><br> 1. Foodservice Consultants
Society International (FCSI). White Paper on Commercial Kitchen Ventilation: Best
Practice Design and Specification Guidelines. September 2006, www.fcsi.org.
2. PG&E Food Service Technology Center. Design Guides for Commercial Kitchen Ventilation
Systems. www.fishnick.com/ckv/designguide/.
3. American Society of Heating,
Refrigeration, and Air Conditioning Engineers. 2003 ASHRAE Handbook —
Applications. Chapter 31, “Kitchen Ventilation.” Atlanta, GA: 2003.
4. Swierczyna, R.T., P.A.
Sobiski, D. Fisher. 1202-RP Effect of appliance diversity and
position on commercial kitchen hood performance. ASHRAE. Atlanta,
GA: 2005.
5. Brohard, G., D.R. Fisher,
P.E., V.A. Smith, P.E., R.T. Swierczyna, P.A. Sobiski. Makeup air
effects on kitchen exhaust hood performance. California Energy
Commission. Sacramento, CA: 2003.
Did you enjoy this article? Click here to subscribe to the magazine.
Click the button below to sign up to receive both of our NEW Newsletters. Receive one now (Controls E-newsletter or IAQ E-newsletter) and the other at a later date, or receive BOTH E-newsletters.
Subscribe Now! Engin- eered Systems provides monthly articles relating to non-residential HVACR equip. and components. Sign up for your FREE subscription today!