|
|
| FIGURE 2. Trend graphic of a constant volume AHU. |
|
The
few periods when the green line (chilled water valve) and red line
(hot water valve) were both more than 60% open were times when the
system was in dehumidification mode (subcooling and then reheating
the supply air). The area of interest, however, was in the center of
the trend graph where the hot water valve was commanded fully closed
(red line is on the 0% line at the bottom of the graph) and the
chilled water valve was modulating between 35% to 40%
open.
With the AHU discharge temperature
(purple) varying between 68°F and 72°, the space temperature (light
blue) was very steady at its 70° setpoint. As such, it would be easy
to conclude that this system was performing very well. The part that
didn’t seem to fit was the mixed air temperature (orange), which
was consistently about 5° lower than the discharge air temperature.
How is it that the mixed air temperature was
being warmed that much with the chilled water valve 35% to 40% open?
In such a small system, heat gain across the fan would not result in
that type of heat load. This trend analysis allowed us to identify
that the hot water control valve was leaking past. Even though its
control system signal (the red line on the trend graph) was 0% open,
the valve was physically not closing fully. If this had gone
unnoticed by the commissioning process, the unnecessary hot water
consumption and compensating chilled water consumption would have
resulted in approximately $4,400/yr in wasted energy for the building
owner.
In the best of all worlds, these types
of trend logs would be collected and analyzed up to three times
during the first year of operation, depending on the local climate:
1) during the winter; 2) during the summer; or 3) during a transition
period, either spring or fall. Of course, the value of such analysis
can also be carried into normal operations, and that is what I will
address in next month’s column.
ES